Technická data
Název:
SIPLUS CMS4000 Interface Node VIB-A
Popis:
SIPLUS CMS - HARDWARE IFN VIB-A ACQUISITION OF ANALOG SIGNALS; DETECTION OF MACHINE VIBRATIONS 6*IEPE-INPUT FOR VIBRATION ACCELERATION MEASUREMENT; UB=24VDC; IP67 MEASUREMENT; UB=24VDC; IP67
Technické informace:
General information | ||
Product brand name | SIPLUS | |
Product designation | IFN VIB-ACC | |
Product description | Six IEPE sensor signals or five IEPE sensor signals and one analog input signal (e.g. for speed) are measured with the IFN VIB-A. | |
Installation type/mounting | ||
Mounting type | standard rail | |
Mounting accessories | Mounting bracket, can be ordered as option | |
Required clearance | ||
● for side-by-side mounting at the front | 80 mm | |
● for side-by-side mounting at the top | 25 mm | |
● for side-by-side mounting at the back | 25 mm | |
Supply voltage | ||
Design of the power supply | stabilized | |
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 32 V | |
Reverse polarity protection | Yes | |
Overvoltage protection | max. 35 V | |
Input current | ||
from external supply (24 V DC), max. | 0.2 A | |
Power | ||
Active power input, max. | 4.8 W | |
Analog inputs | ||
Number of analog inputs | 1 | |
Designation of the analog input | CH6 | |
Measured variable | Voltage | |
Connector type | Connector plug 5-pole (M12) | |
Electrical input frequency, min. | 0 Hz | |
Electrical input frequency, max. | 1 kHz | |
Overvoltage strength, min. | -60 V | |
Overvoltage strength, max. | 60 V | |
Short-circuit detection | No | |
Input ranges (rated values), voltages | ||
● At DC, min. | -30 V | |
Input ranges (rated values), currents | ||
● with DC | 0.012 mA | |
Analog value generation for the inputs | ||
Parameterizable down sampling frequencies | 4 / 8 / 16 / 24 / 48 / 64 / 96 kHz | |
Sampling frequency, max. | 192 kHz | |
Integration and conversion time/resolution per channel | ||
● Resolution with override range (bit including sign) | 16 bit | |
Sensor input | ||
Number of sensor inputs | 6 | |
Designation of the sensor inputs | CH1 ... CH6 | |
Design of the sensor | IEPE | |
Overvoltage strength, min. | -60 V | |
Overvoltage strength, max. | 60 V | |
Short-circuit detection | Yes | |
Encoder signals, IEPE | ||
● Electrical input frequency, min. | 0.1 Hz | |
● Electrical input frequency, max. | 40 kHz | |
● Parameterizable down sampling frequencies | 0.014 / 0,33 / 4 / 8 / 16 / 24 / 48 / 64 / 96 kHz | |
● Resolution with override range (bit including sign) | 16 bit | |
Errors/accuracies | ||
Relative measuring accuracy for analog input signals, min. | -1 % | |
Relative measuring accuracy for analog input signals, max. | 1 % | |
Relative measuring accuracy for IEPE signals, min. | -0.7 % | |
Relative measuring accuracy for IEPE signals, max. | 0.7 % | |
Crosstalk attenuation between analog input signals at 1 kHz | -78 dB | |
Crosstalk attenuation between sensor channels CH 1 and CH 2 at 1 kHz | -69 dB | |
Crosstalk attenuation between sensor channels CH 3 ... CH 6 at 1 kHz | -73 dB | |
Signal-to-noise ratio for analog input signals | -69 dB | |
Signal-to-noise ratio between sensor channels CH 1 and CH 2 for IEPE signals | -57 dB | |
Signal-to-noise ratio between sensor channels CH 3 ... CH 6 for IEPE signals | -70 dB | |
Interfaces | ||
Number of interfaces | 3 | |
Transmission rate | 400 Mbit/s | |
Protocols | ||
Protocol | IEEE 1394a/b | |
Potential separation | ||
Potential separation analog inputs | ||
● Potential separation analog inputs | No | |
Galvanic isolation at sensor input | ||
● Galvanic isolation at sensor input | No | |
Degree and class of protection | ||
IP degree of protection | IP67 | |
Standards, approvals, certificates | ||
CE mark | Yes | |
RCM (formerly C-TICK) | Yes | |
KC approval | Yes | |
EAC (formerly Gost-R) | Yes | |
China RoHS compliance | Yes | |
Use in hazardous areas | ||
● ATEX | Yes | |
● IECEx | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -40 °C | |
● max. | 65 °C | |
Ambient temperature during storage/transportation | ||
● Storage, min. | -40 °C | |
● Storage, max. | 85 °C | |
● Transportation, min. | -40 °C | |
● Transportation, max. | 85 °C | |
Connection method | ||
Design of electrical connection for the PE conductor | M4 screw with contact washer | |
● Connectable conductor cross-section for PE terminal | 2.5 mm² | |
Design of plug-in connection | Connector plug 8-pole (M12) | |
Design of the pin assignment of the inputs | Male connector 5-pole (M12) | |
Mechanics/material | ||
Material of housing | aluminum | |
Dimensions | ||
Width | 86 mm | |
Height | 210 mm | |
Depth | 87 mm | |
Width when mounted on DIN rail | 86 mm | |
Height when mounted on DIN rail | 210 mm | |
Depth when mounted on DIN rail | 96 mm | |
Weights | ||
Weight (without packaging) | 1.24 kg | |
last modified: | 02/01/2017 |