Technická data
Název:
SIPLUS LOGO! AM2 AQ V8
Popis:
SIPLUS LOGO! AM2 AQ -40 ... +70 DEGREES C STARTUP -25 GDEGREES C WITH CONFORMAL COATING BASED ON 6ED1055-1MM00-0BA2 . EXPAN. MODULE, PU: DC 24V, 0/4-20MA 2AQ, 0-10V FOR LOGO! 8
Technické informace:
Installation type/mounting | ||
Mounting | on 35 mm DIN rail, 2 spacing units wide | |
Supply voltage | ||
Rated value (DC) | ||
● 12 V DC | No | |
● 24 V DC | Yes | |
Analog outputs | ||
Number of analog outputs | 2 | |
Output ranges, voltage | ||
● 0 to 10 V | Yes | |
Output ranges, current | ||
● 0 to 20 mA | Yes | |
● 4 mA to 20 mA | Yes | |
EMC | ||
Emission of radio interference acc. to EN 55 011 | ||
● Limit class B, for use in residential areas | Yes | |
Degree and class of protection | ||
Degree of protection acc. to EN 60529 | ||
● IP20 | Yes | |
Standards, approvals, certificates | ||
CE mark | Yes | |
developed in accordance with IEC 61131 | Yes | |
according to VDE 0631 | Yes | |
Marine approval | ||
● Marine approval | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -40 °C; = Tmin; Startup @ -25 °C | |
● max. | 70 °C; = Tmax | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
● At cold restart, min. | -25 °C | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 35.5 mm | |
Height | 90 mm | |
Depth | 58 mm | |
last modified: | 02/01/2017 |