Technická data
Název:
SIPLUS LOGO! DM16 24R V8
Popis:
SIPLUS LOGO! DM16 24R -40 ... +70 DEGREES C STARTUP -25 DEGREES C MIT CONFORMAL COATING BASED ON 6ED1055-1NB10-0BA2 . EXP. MODULE, PU/I/O: 24V DC/24V DC/RELAY, 8 DI/8 DO, 4TE FOR LOGO! 8
Technické informace:
Installation type/mounting | ||
Mounting | on 35 mm DIN rail, 4 spacing units wide | |
Supply voltage | ||
Rated value (DC) | ||
● 24 V DC | Yes | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
Rated value (AC) | ||
● 24 V AC | No | |
Digital inputs | ||
Number of digital inputs | 8 | |
Input voltage | ||
● Type of input voltage | DC | |
● for signal "0" | < 5 V DC | |
● for signal "1" | > 12 V DC | |
Input current | ||
● for signal "0", max. (permissible quiescent current) | 0.85 mA | |
● for signal "1", typ. | 3.5 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— at "0" to "1", max. | 1.5 ms | |
— at "1" to "0", max. | 1.5 ms | |
Digital outputs | ||
Number of digital outputs | 8; Relays | |
Short-circuit protection | No | |
Controlling a digital input | Yes | |
Switching capacity of the outputs | ||
● on lamp load, max. | 1 000 W | |
Output current | ||
● for signal "1" rated value | 5 A | |
● for signal "1" minimum load current | 100 mA | |
Parallel switching of two outputs | ||
● for uprating | No | |
Switching frequency | ||
● with resistive load, max. | 2 Hz | |
● with inductive load, max. | 0.5 Hz | |
● mechanical, max. | 10 Hz | |
Relay outputs | ||
Switching capacity of contacts | ||
— with inductive load, max. | 3 A | |
— with resistive load, max. | 5 A | |
EMC | ||
Emission of radio interference acc. to EN 55 011 | ||
● Limit class B, for use in residential areas | Yes | |
Degree and class of protection | ||
Degree of protection acc. to EN 60529 | ||
● IP20 | Yes | |
Standards, approvals, certificates | ||
CE mark | Yes | |
developed in accordance with IEC 61131 | Yes | |
according to VDE 0631 | Yes | |
Marine approval | ||
● Marine approval | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -40 °C; = Tmin; Startup @ -25 °C | |
● max. | 70 °C; = Tmax; Tmax > +55 °C max. load 3 A per relay | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Extended ambient conditions | ||
● At cold restart, min. | -25 °C | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 71.5 mm | |
Height | 90 mm | |
Depth | 58 mm | |
last modified: | 02/01/2017 |