Technická data
Název:
SIPLUS NET SCALANCE X104-2
Popis:
SIPLUS NET SCALANCE X104-2 -25 ... +60 DEGREE C WITH CONFORMAL COATING BASED ON 6GK5104-2BB00-2AA3
Technické informace:
Product type designation | SIPLUS SCALANCE X104-2 | |
Transmission rate | ||
Transfer rate | 10 Mbit/s, 100 Mbit/s | |
Interfaces / for communication / integrated | ||
Number of electrical connections | ||
● for network components or terminal equipment | 4 | |
Interfaces / others | ||
Number of electrical connections | ||
● for signaling contact | 1 | |
● for power supply | 1 | |
● for redundant voltage supply | 1 | |
Type of electrical connection | ||
● for signaling contact | 2-pole terminal block | |
● for power supply | 4-pole terminal block | |
Signal-Inputs/outputs | ||
Operating voltage / of the signaling contacts | ||
● at DC / Rated value | 24 V | |
Operating current / of the signaling contacts | ||
● at DC / maximum | 0.1 A | |
Supply voltage, current consumption, power loss | ||
Type of voltage / of the supply voltage | DC | |
Supply voltage | ||
● external | 24 V | |
● external | 18 ... 32 V | |
Product component / fusing at power supply input | Yes | |
Fuse protection type / at input for supply voltage | 0.6 A / 60 V | |
Consumed current / maximum | 0.175 A | |
Power loss [W] | ||
● at DC / at 24 V | 3.8 W | |
Permitted ambient conditions | ||
Ambient temperature | ||
● during operation | -25 ... +60 °C | |
● during storage | -40 ... +80 °C | |
● during transport | -40 ... +80 °C | |
Relative humidity | ||
● at 25 °C / without condensation / during operation / maximum | 100 % | |
● with condensation / maximum | 100 %; r.F., incl. condensation/frost permitted (no commissioning in bedewed state) | |
Ambient condition / relating to ambient temperature - air pressure - installation altitude | -25 ... +60°C at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // -25 ... +50°C at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // -25 ... +40°C at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Resistance to biologically active substances / conformity acc. to EN 60721-3-3 | Yes; Compliance with EN 60721-3-3, Class 3B2 mold, fungus, and sponge spores (except fauna). The supplied plug covers must remain in place over the unused interfaces during operation! | |
Resistance to chemically active substances / conformity acc. to EN 60721-3-3 | Yes; Compliance with EN 60721-3-3, class 3C4 incl. salt spray according to EN 60068-2-52 (severity 3). The supplied plug covers must remain in place over the unused interfaces during operation! | |
Resistance to mechanically active substances / conformity acc. to EN 60721-3-3 | Yes; Compliance with EN 60721-3-3, Class 3S4 including sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation! | |
Protection class IP | IP30 | |
Design, dimensions and weight | ||
Design | compact | |
Width | 60 mm | |
Height | 125 mm | |
Depth | 124 mm | |
Net weight | 0.78 kg | |
Mounting type | ||
● 35 mm DIN rail mounting | Yes | |
● wall mounting | Yes | |
● S7-300 rail mounting | Yes | |
Product functions / management, configuration | ||
Product function | ||
● switch-managed | No | |
Standards, specifications, approvals | ||
Standard | ||
● for hazardous zone | EN 60079-0: 2006, EN60079-15: 2005, II 3 G Ex nA IIT.., KEMA 07 ATEX 0145 X | |
● for emitted interference | EN 61000-6-4 (Class A) | |
● for interference immunity | EN 61000-6-2 | |
Certificate of suitability / CE marking | Yes | |
Certificate of suitability | EN 61000-6-2, EN 61000-6-4 | |
● Railway application in accordance with EN 50155 | No | |
● Railway application in accordance with EN 50124-1 | No | |
● KC approval | Yes | |
Marine classification association | ||
● American Bureau of Shipping Europe Ltd. (ABS) | No | |
● Bureau Veritas (BV) | No | |
● Det Norske Veritas (DNV) | No | |
● Germanische Lloyd (GL) | No | |
● Lloyds Register of Shipping (LRS) | No | |
● Nippon Kaiji Kyokai (NK) | No | |
● Polski Rejestr Statkow (PRS) | No | |
Further Information / Internet Links | ||
Internet-Link | ||
● to website: Selector SIMATIC NET SELECTION TOOL | http://www.siemens.com/snst | |
● to website: Industrial communication | http://www.siemens.com/simatic-net | |
● to website: Industry Mall | https://mall.industry.siemens.com | |
● to website: Information and Download Center | http://www.siemens.com/industry/infocenter | |
● to website: Image database | http://automation.siemens.com/bilddb | |
● to website: CAx Download Manager | http://www.siemens.com/cax | |
● to website: Industry Online Support | https://support.industry.siemens.com | |
Security information | ||
Security information | Siemens provides products and solutions with industrial security functions that support the secure operation of plants, solutions, machines, equipment and/or networks. They are important components in a holistic industrial security concept. With this in mind, Siemens’ products and solutions undergo continuous development. Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action(e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept. Third-party products that may be in use should also be considered. For more information about industrial security, visit http://www.siemens.com/industrialsecurity. To stay informed about product updates as they occur, sign up for a product-specific newsletter. For more information, visit http://support.automation.siemens.com. (V3.4) | |
last modified: | 02/02/2017 |