Technická data
Název:
SIPLUS power DC 24V 0.375A
Popis:
SIPLUS PS 24V/0.375A DEW ALLOWABLE IN: 48 ... 220 VDC OUT: 24VDC/0.375A BASED ON 6EP1731-2BA00
Technické informace:
SIPLUS PS 24V/0.375A DEW ALLOWABLE IN: 48 ... 220 VDC OUT: 24VDC/0.375A BASED ON 6EP1731-2BA00 | ||
Input | ||
Input | DC voltage | |
Supply voltage | ||
● at DC | 48 ... 220 V | |
Voltage range AC | 30 ... 187 V | |
Input voltage | ||
● at DC | 30 ... 264 V | |
Wide-range input | Yes | |
Overvoltage resistance | - | |
Mains buffering at Iout rated, min. | 10 ms; at Vin = 220 V | |
Input current | ||
● at rated input voltage 48 V | 0.3 A | |
● at rated input voltage 220 V | 0.06 A | |
Switch-on current limiting (+25 °C), max. | 35 A | |
Duration of inrush current limiting at 25 °C | ||
● typical | 3 ms | |
I²t, max. | 1.2 A²·s | |
Built-in incoming fuse | F 4 A/250 V (not accessible) | |
Protection in the mains power input (IEC 898) | Recommended miniature circuit breaker: from 6 A characteristic C, suitable for DC | |
Output | ||
Output | Controlled, isolated DC voltage | |
Rated voltage Vout DC | 24 V | |
Total tolerance, static ± | 3 % | |
Static mains compensation, approx. | 0.1 % | |
Static load balancing, approx. | 0.1 % | |
Residual ripple peak-peak, max. | 150 mV | |
Residual ripple peak-peak, typ. | 50 mV | |
Spikes peak-peak, max. (bandwidth: 20 MHz) | 240 mV | |
Spikes peak-peak, typ. (bandwidth: 20 MHz) | 50 mV | |
Product function Output voltage adjustable | No | |
Output voltage setting | - | |
Status display | Green LED for 24 V OK | |
On/off behavior | No overshoot of Vout (soft start) | |
Startup delay, max. | 2.5 s | |
Voltage rise, typ. | 90 ms | |
Rated current value Iout rated | 0.375 A | |
Current range | 0 ... 0.375 A | |
● Note | +60 ... +70 °C: Derating 3%/K | |
Supplied active power typical | 9 W | |
Short-term overload current | ||
● at short-circuit during operation typical | 2.7 A | |
Duration of overloading capability for excess current | ||
● at short-circuit during operation | 200 ms | |
Parallel switching for enhanced performance | No | |
Efficiency | ||
Efficiency at Vout rated, Iout rated, approx. | 66 % | |
Power loss at Vout rated, Iout rated, approx. | 4.6 W | |
Closed-loop control | ||
Dynamic mains compensation (Vin rated ±15 %), max. | 0.3 % | |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. | 0.4 % | |
Load step setting time 50 to 100%, typ. | 2 ms | |
Load step setting time 100 to 50%, typ. | 2 ms | |
Protection and monitoring | ||
Output overvoltage protection | Yes, according to EN 60950-1 | |
Current limitation | 0.41 ... 0.49 A | |
Property of the output Short-circuit proof | Yes | |
Short-circuit protection | Electronic shutdown, automatic restart | |
Enduring short circuit current RMS value | ||
● maximum | 0.9 A | |
Overload/short-circuit indicator | - | |
Safety | ||
Primary/secondary isolation | Yes | |
Galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | |
Protection class | Class I | |
Leakage current | ||
● maximum | 3.5 mA | |
CE mark | Yes | |
UL/cUL (CSA) approval | cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289, cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273 | |
Explosion protection | - | |
FM approval | - | |
CB approval | No | |
Marine approval | - | |
Degree of protection (EN 60529) | IP20 | |
EMC | ||
Emitted interference | EN 55022 Class B | |
Supply harmonics limitation | not applicable | |
Noise immunity | EN 61000-6-2 | |
Operating data | ||
Ambient temperature | ||
● during operation | -25 ... +70 °C | |
— Note | with natural convection | |
● during transport | -40 ... +70 °C | |
● during storage | -40 ... +70 °C | |
Humidity class according to EN 60721 | Climate class 3K8H | |
Relative humidity with condensation maximum | 100 %; Relative humidity, incl. condensation/frost permitted (no commissioning under condensation conditions) | |
Resistance to biologically active substances conformity acc. to EN 60721-3-3 | Yes; Compliant with EN 60721-3-3, Class 3B2 mold and fungal spores (except fauna); the supplied plug covers must remain in place on the unused interfaces during operation. | |
Resistance to chemically active substances conformity acc. to EN 60721-3-3 | Yes; Compliant with EN 60721-3-3, Class 3C4 incl. salt spray in accordance with EN 60068-2-52 (severity 3); the supplied plug covers must remain in place on the unused interfaces during operation. | |
Resistance to mechanically active substances conformity acc. to EN 60721-3-3 | Yes; Conformity with EN 60721-3-3, Class 3S4 incl. Sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Mechanics | ||
Connection technology | screw-type terminals | |
Connections | ||
● Supply input | L+1, M1, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded | |
● Output | +: 1 screw terminal for 0.5 ... 2.5 mm²; -: 2 screw terminals for 0.5 ... 2.5 mm² | |
Width of the enclosure | 22.5 mm | |
Height of the enclosure | 80 mm | |
Depth of the enclosure | 91 mm | |
Required spacing | ||
● top | 50 mm | |
● bottom | 50 mm | |
● left | 0 mm | |
● right | 0 mm | |
Weight, approx. | 0.14 kg | |
Product feature of the enclosure housing for side-by-side mounting | Yes | |
Installation | Snaps onto DIN rail EN 60715 35x7.5/15 | |
MTBF at 40 °C | 1 466 123 h | |
Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |