Technická data
Název:
SIPLUS_PS307_10A
Popis:
SIPLUS S7-300 PS 307 10A -25 ... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7307-1KA02-0AA0 . STABILIZED POWER SUPPLY PS307 INPUT: 120/230 V AC OUTPUT: 24 V DC/10 A
Technické informace:
Supply voltage | ||
Rated value (AC) | ||
● 120 V AC | Yes; 85 to 132 V AC | |
● 230 V AC | Yes; 170 to 264 V AC | |
Overvoltage strength | 2.3x Ue rated, 1.3 ms | |
Line frequency | ||
● permissible range, lower limit | 47 Hz | |
● permissible range, upper limit | 63 Hz | |
Mains buffering | ||
● Mains/voltage failure stored energy time | 20 ms; min., for Ia rated and Ue = 93 / 187 V | |
● Repeat rate, min. | 1 s | |
Input current | ||
Rated value at 120 V AC | 4.2 A | |
Rated value at 230 V AC | 1.9 A | |
Inrush current, max. | 55 A; max. at 25 °C, duration max. 3 ms | |
I²t | 3.3 A²·s | |
Leakage current, typ. | 0.6 mA | |
Leakage current, max. | 3.5 mA | |
Overcurrent overload capability | 80 ms on short circuit during startup and operation | |
Output voltage | ||
Rated value (DC) | 24 V; stable at no-load max. 2.5 s | |
permissible range, lower limit (DC) | 23.27 V | |
permissible range, upper limit (DC) | 24.72 V | |
Power up time, max. | 2 s | |
Voltage rise time, typ. | 10 ms | |
Overvoltage protection | Additional control circuit, cutoff at < 28.8 V, automatic restart | |
Short-circuit strength | electronic trip, automatic restart | |
Residual ripple, typ. | 15 mV; Peak - peak | |
Residual ripple, max. | 50 mV; Peak - peak | |
Output current | ||
Current output (rated value) | 10 A; 7 A @ > 60 °C, can be switched in parallel | |
Short-circuit protection | Yes; Electronic | |
Continuous short-circuit current, max. | 12 A | |
Power | ||
Active power input, typ. | 240 W | |
Efficiency | 90 %; approx., at Ua rated, Ia rated | |
Power loss | ||
Power loss, typ. | 27 W; approx., at Ua rated, Ia rated | |
Interrupts/diagnostics/status information | ||
Diagnostics indication LED | ||
● Output voltage 24 V DC (green) | Yes; OK for 24 V | |
Potential separation | ||
primary/secondary | Yes; SELV output voltage Ua according to EN 60950-1 and EN 50178 | |
SELV | Yes | |
Isolation | ||
Isolation tested with | Rated insulation voltage (24 V against L1) 250 V AC, tested with 4 200 V DC | |
EMC | ||
EMC interference immunity | EN 61000-6-2 | |
EMC interference emission | EN 55022 Class B | |
Degree and class of protection | ||
IP degree of protection | IP20 | |
Protection class | 1; with protective conductor | |
Standards, approvals, certificates | ||
CE mark | Yes | |
Standard for line harmonics limit | EN 61000-3-2 | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -25 °C; = Tmin | |
● max. | 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 80 mm | |
Height | 125 mm | |
Depth | 120 mm | |
Weights | ||
Weight, approx. | 0.8 kg | |
last modified: | 02/03/2017 |