Technická data
Název:
SIPLUS S7-1200 SM 1223 16DI/16DQ RLY
Popis:
SIPLUS S7-1200 SM1223 16DI/16DQ RLY FOR MEDIAL STRESS WITH CONFORMAL COATING BASED ON 6ES7223-1PL32-0XB0 . DIGITAL I/O 16DI / 16DQ, 16DI DC 24 V, SINK/SOURCE, 16DQ, RELAY 2A
Technické informace:
Supply voltage | ||
Rated value (DC) | ||
● 24 V DC | Yes | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
Input current | ||
from backplane bus 5 V DC, max. | 180 mA | |
Digital inputs | ||
● from load voltage L+ (without load), max. | 4 mA/input 11 mA/relay | |
Output voltage | ||
Power supply to the transmitters | ||
● present | Yes | |
Power loss | ||
Power loss, typ. | 10 W | |
Digital inputs | ||
Number of digital inputs | 16 | |
● in groups of | 2 | |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes | |
Number of simultaneously controllable inputs | ||
all mounting positions | ||
— up to 40 °C, max. | 16 | |
horizontal installation | ||
— up to 40 °C, max. | 16 | |
— up to 50 °C, max. | 16 | |
vertical installation | ||
— up to 40 °C, max. | 16 | |
Input voltage | ||
● Type of input voltage | DC | |
● Rated value (DC) | 24 V | |
● for signal "0" | 5 V DC at 1 mA | |
● for signal "1" | 15 V DC at 2.5 mA | |
Input current | ||
● for signal "0", max. (permissible quiescent current) | 1 mA | |
● for signal "1", min. | 2.5 mA | |
● for signal "1", typ. | 4 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— parameterizable | Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | |
for interrupt inputs | ||
— parameterizable | Yes | |
Cable length | ||
● shielded, max. | 500 m | |
● unshielded, max. | 300 m | |
Digital outputs | ||
Number of digital outputs | 16 | |
● in groups of | 4 | |
Short-circuit protection | No; to be provided externally | |
Switching capacity of the outputs | ||
● with resistive load, max. | 2 A | |
● on lamp load, max. | 30 W with DC, 200 W with AC | |
Output voltage | ||
● Rated value (DC) | 5 V DC to 30 V DC | |
● Rated value (AC) | 5 V AC to 250 V AC | |
Output current | ||
● for signal "1" permissible range, max. | 2 A | |
Output delay with resistive load | ||
● "0" to "1", max. | 10 ms | |
● "1" to "0", max. | 10 ms | |
Total current of the outputs (per group) | ||
horizontal installation | ||
— up to 50 °C, max. | 8 A; Current per mass | |
Relay outputs | ||
● Number of relay outputs | 16 | |
● Rated supply voltage of relay coil L+ (DC) | 24 V | |
● Number of operating cycles, max. | mechanically 10 million, at rated load voltage 100 000 | |
Switching capacity of contacts | ||
— with inductive load, max. | 2 A | |
— on lamp load, max. | 30 W with DC, 200 W with AC | |
— with resistive load, max. | 2 A | |
Cable length | ||
● shielded, max. | 500 m | |
● unshielded, max. | 150 m | |
Interrupts/diagnostics/status information | ||
Alarms | Yes | |
Diagnostic functions | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
Diagnostic messages | ||
● Monitoring the supply voltage | Yes | |
Diagnostics indication LED | ||
● for status of the inputs | Yes | |
● for status of the outputs | Yes | |
● for maintenance | Yes | |
● Status indicator digital input (green) | Yes | |
● Status indicator digital output (green) | Yes | |
Potential separation | ||
Potential separation digital inputs | ||
● between the channels, in groups of | 2 | |
Potential separation digital outputs | ||
● between the channels | Relays | |
● between the channels, in groups of | 4 | |
● between the channels and backplane bus | 1500 V AC for 1 minute | |
Permissible potential difference | ||
between different circuits | 750 V AC for 1 minute | |
Degree and class of protection | ||
Degree of protection acc. to EN 60529 | ||
● IP20 | Yes | |
Standards, approvals, certificates | ||
CE mark | Yes | |
Ambient conditions | ||
Free fall | ||
● Fall height, max. | 0.3 m; five times, in product package | |
Ambient temperature during operation | ||
● min. | -20 °C; = Tmin; Startup @ 0 °C | |
● max. | 60 °C; = Tmax | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Connection method | ||
required front connector | Yes | |
Mechanics/material | ||
Enclosure material (front) | ||
● Plastic | Yes | |
Dimensions | ||
Width | 70 mm | |
Height | 100 mm | |
Depth | 75 mm | |
Weights | ||
Weight, approx. | 350 g | |
last modified: | 02/01/2017 |