Technická data
Název:
SIPLUS S7-1200 SB 1223 2DI/2DQ 5VDC
Popis:
SIPLUS S7-1200 SB1223 E/A -40...+60°C, Startup -25°C WITH CONFORMAL COATING BASED ON 6ES7223-3AD30-0XB0 . DIGITALE E/A 2DI/2DO, 5VDC 200KHZ
Technické informace:
Input current | ||
from backplane bus 5 V DC, typ. | 50 mA | |
Output voltage | ||
Power supply to the transmitters | ||
● Supply current, max. | 4 mA; per channel | |
Power loss | ||
Power loss, typ. | 1 W | |
Digital inputs | ||
Number of digital inputs | 2 | |
● in groups of | 1 | |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes | |
Number of simultaneously controllable inputs | ||
all mounting positions | ||
— up to 40 °C, max. | 2 | |
Input voltage | ||
● Rated value (DC) | 5 V | |
● for signal "0" | 0 to 1 V | |
● for signal "1" | 2 to 6 V | |
Input current | ||
● for signal "0", max. (permissible quiescent current) | 3 mA | |
● for signal "1", min. | 6 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— parameterizable | Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | |
— at "0" to "1", max. | 2 µs | |
for interrupt inputs | ||
— parameterizable | Yes | |
for counter/technological functions | ||
— parameterizable | Yes | |
Cable length | ||
● shielded, max. | 50 m | |
Digital outputs | ||
Number of digital outputs | 2 | |
● in groups of | 1 | |
Switching capacity of the outputs | ||
● with resistive load, max. | 0.1 A | |
Load resistance range | ||
● upper limit | 5 Ω | |
Output voltage | ||
● Rated value (DC) | 5 V | |
● for signal "0", max. | 0.4 V | |
● for signal "1", min. | L+ (-0.5 V) | |
● for signal "1", max. | 6 V | |
Output current | ||
● for signal "1" rated value | 0.1 A | |
● for signal "1" permissible range, max. | 0.11 A | |
Cable length | ||
● shielded, max. | 50 m | |
Interrupts/diagnostics/status information | ||
Alarms | Yes | |
Diagnostic functions | Yes | |
Diagnostics indication LED | ||
● for status of the inputs | Yes | |
● for status of the outputs | Yes | |
Degree and class of protection | ||
Degree of protection acc. to EN 60529 | ||
● IP20 | Yes | |
Standards, approvals, certificates | ||
CE mark | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -40 °C; = Tmin; Startup @ -25 °C | |
● max. | 60 °C; = Tmax | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Mechanics/material | ||
Enclosure material (front) | ||
● Plastic | Yes | |
Dimensions | ||
Width | 38 mm | |
Height | 62 mm | |
Depth | 21 mm | |
Weights | ||
Weight, approx. | 40 g | |
last modified: | 02/01/2017 |