Technická data
Název:
SIPLUS S7-1200 SM 1226 F-DI 16x24VDC
Popis:
SIPLUS S7-1200 SM 1226 F-DI 16X24VDC -25 ... +60 GRAD C WITH CONFORMAL COATING BASED ON: 6ES7226-6BA32-0XB0 F-DI 16X 24VDC, PROFISAFE, 70 MM WIDTH, UP TO PL E (ISO 13849-1)/ UP TO SIL3 (IEC 61508)
Technické informace:
Supply voltage | ||
Rated value (DC) | ||
● 24 V DC | Yes | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
Input current | ||
from backplane bus 5 V DC, max. | 155 mA; Current consumption (SM Bus, 5 V DC): 155 mA | |
Digital inputs | ||
● from load voltage L+ (without load), max. | 130 mA; 130 mA + 6 mA / input used + any Vs1/Vs2 current used | |
Power loss | ||
Power loss, typ. | 7 W | |
Digital inputs | ||
Number of digital inputs | 16; 16 (1oo1) or 8 (1oo2); Note: You can individually assign each pair of inputs "a.x" and "b.x" as a single (1oo2)-channel or as 2 separate (1oo1)-channels | |
Number of simultaneously controllable inputs | ||
horizontal installation | ||
— up to 50 °C, max. | 16; 16 inputs at 55 °C horizontal | |
vertical installation | ||
— up to 40 °C, max. | 16; 16 inputs at 45 °C vertical | |
Input voltage | ||
● for signal "0" | -30 V DC to +5 V DC | |
● for signal "1" | 15 V DC to 30 V DC | |
Input current | ||
● for signal "0", max. (permissible quiescent current) | 0.5 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— parameterizable | Yes; 0.8 / 1.6 / 3.2 / 6.4 / 12.8 ms | |
Cable length | ||
● shielded, max. | 200 m; Unshielded with input filter time of 1.6 ms to 12.6 ms (With an input delay of 0.8 ms, shielded cables must be used for the digital inputs and the sensor supply) | |
● unshielded, max. | 200 m; Shielded with input filter time of 0.8 ms to 12.6 s (With an input delay of 0.8 ms, shielded cables must be used for the digital inputs and the sensor supply) | |
Interrupts/diagnostics/status information | ||
Diagnostics indication LED | ||
● for status of the inputs | Yes | |
Standards, approvals, certificates | ||
CE mark | Yes | |
cULus | Yes | |
FM approval | No | |
Highest safety class achievable in safety mode | ||
● Performance level according to ISO 13849-1 | 1-channel, Category 3, PL d; 2-channel, Category 3 or 4, PL e | |
● SIL acc. to IEC 61508 | SIL 2 (single-channel), SIL 3 (two-channel) | |
Ambient conditions | ||
Free fall | ||
● Fall height, max. | 0.3 m; five times, in product package | |
Ambient temperature during operation | ||
● min. | -25 °C; = Tmin | |
● max. | 55 °C; = Tmax | |
● permissible temperature change | 5°C to 55°C, 3°C / minute | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Mechanics/material | ||
Enclosure material (front) | ||
● Plastic | Yes | |
Dimensions | ||
Width | 70 mm | |
Height | 100 mm | |
Depth | 75 mm | |
Weights | ||
Weight, approx. | 250 g | |
last modified: | 02/01/2017 |