Technická data
Název:
SIPLUS S7-1200 SM 1226 F-DQ 4x24VDC
Popis:
SIPLUS S7-1200 SM 1226 F-DQ 4X24VDC -25 ... +60 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7226-6DA32-0XB0 . SM 1226, F-DQ 4X 24VDC 2A, PROFISAFE, 70 MM WIDTH, UP TO PL E (ISO 13849-1)/ UP TO SIL3 (IEC 61508)
Technické informace:
Supply voltage | ||
Rated value (DC) | ||
● 24 V DC | Yes | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
Input current | ||
from backplane bus 5 V DC, max. | 125 mA | |
Digital outputs | ||
● from load voltage L+, max. | 170 mA | |
Power loss | ||
Power loss, typ. | 8 W | |
Digital outputs | ||
Number of digital outputs | 4 | |
● in groups of | 1 | |
Short-circuit protection | Yes | |
Switching capacity of the outputs | ||
● with resistive load, max. | 30 Hz | |
● on lamp load, max. | 10 Hz | |
Output voltage | ||
● Rated value (DC) | 24 V | |
Output current | ||
● for signal "1" rated value | 2 A | |
● for signal "1" permissible range, max. | 10 mA to 2.4 A | |
● for signal "0" residual current, max. | P-switch: 0.5 mA, maximum; M-switch: 0.5 mA, maximum | |
Cable length | ||
● shielded, max. | 200 m | |
● unshielded, max. | 200 m | |
Interrupts/diagnostics/status information | ||
Diagnostics indication LED | ||
● for status of the outputs | Yes | |
Standards, approvals, certificates | ||
CE mark | Yes | |
cULus | Yes | |
FM approval | No | |
Highest safety class achievable in safety mode | ||
● Performance level according to ISO 13849-1 | Category 4, PL e | |
● SIL acc. to IEC 61508 | SIL 3 | |
Ambient conditions | ||
Free fall | ||
● Fall height, max. | 0.3 m; five times, in product package | |
Ambient temperature during operation | ||
● min. | -25 °C; = Tmin | |
● max. | 55 °C; = Tmax | |
● permissible temperature change | 5°C to 55°C, 3°C / minute | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Mechanics/material | ||
Enclosure material (front) | ||
● Plastic | Yes | |
Dimensions | ||
Width | 70 mm | |
Height | 100 mm | |
Depth | 75 mm | |
Weights | ||
Weight, approx. | 270 g | |
last modified: | 02/01/2017 |