Technická data
Název:
SIPLUS S7-1200 CB 1241 RS485
Popis:
SIPLUS S7-1200 CB 1241, -25 ... +60 GRAD C WITH CONFORMAL COATING BASED ON 6ES7241-1CH30-1XB0 RS485
Technické informace:
Input current | ||
from backplane bus 5 V DC, typ. | 50 mA | |
Power loss | ||
Power loss, typ. | 1.5 W | |
Interrupts/diagnostics/status information | ||
Diagnostic functions | Yes | |
Diagnostics indication LED | ||
● for status of the outputs | Yes | |
Degree and class of protection | ||
Degree of protection acc. to EN 60529 | ||
● IP20 | Yes | |
Standards, approvals, certificates | ||
CE mark | Yes | |
RCM (formerly C-TICK) | Yes | |
KC approval | Yes | |
Ambient conditions | ||
Free fall | ||
● Fall height, max. | 0.3 m; five times, in product package | |
Ambient temperature during operation | ||
● min. | -40 °C; = Tmin; Startup @ -25 °C | |
● max. | 55 °C | |
● permissible temperature change | 5°C to 55°C, 3°C / minute | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Air pressure acc. to IEC 60068-2-13 | ||
● Operation, min. | 795 hPa | |
● Operation, max. | 1 080 hPa | |
● Storage/transport, min. | 660 hPa | |
● Storage/transport, max. | 1 080 hPa | |
Relative humidity | ||
● permissible range (without condensation) at 25 °C | 95 % | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
● At cold restart, min. | -25 °C | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Pollutant concentrations | ||
— SO2 at RH < 60% without condensation | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Mechanics/material | ||
Enclosure material (front) | ||
● Plastic | Yes | |
Dimensions | ||
Width | 38 mm | |
Height | 62 mm | |
Depth | 21 mm | |
Weights | ||
Weight, approx. | 40 g | |
last modified: | 02/01/2017 |