Technická data
Název:
SIPLUS ET200S 2AO U high feature
Popis:
SIPLUS ET200S 2AO U HIGH FEATURE -25 ... +60 DEGREES C BASED ON 6ES7135-4LB02-0AB0
Technické informace:
Supply voltage | ||
Load voltage L+ | ||
● Rated value (DC) | 24 V | |
● Reverse polarity protection | Yes | |
Input current | ||
from load voltage L+ (without load), max. | 80 mA | |
from backplane bus 3.3 V DC, max. | 10 mA | |
Power loss | ||
Power loss, max. | 1.2 W | |
Address area | ||
Address space per module | ||
● Address space per module, max. | 4 byte | |
Analog outputs | ||
Number of analog outputs | 2 | |
Voltage output, short-circuit protection | Yes | |
Voltage output, short-circuit current, max. | 25 mA | |
Cycle time (all channels) max. | 0.5 ms; At max. 0.5 µF | |
Output ranges, voltage | ||
● 1 V to 5 V | Yes | |
● -5 V to +5 V | Yes | |
● -10 V to +10 V | Yes | |
Connection of actuators | ||
● for voltage output two-wire connection | Yes | |
● for voltage output four-wire connection | Yes | |
Load impedance (in rated range of output) | ||
● with voltage outputs, min. | 1 kΩ | |
● with voltage outputs, capacitive load, max. | 0.5 µF | |
Destruction limits against externally applied voltages and currents | ||
● Voltages at the outputs towards MANA | 15 V; max. 15 V continuous; 75 V for max. 1 s (mark to space ratio 1:20) | |
Cable length | ||
● shielded, max. | 200 m; 100m if Twa < 2ms | |
Analog value generation for the outputs | ||
Integration and conversion time/resolution per channel | ||
● Resolution with overrange (bit including sign), max. | 16 bit; 15 bit + sign | |
Settling time | ||
● for resistive load | 0.2 ms | |
● for capacitive load | 0.5 ms; At max. 0.5 µF | |
● for inductive load | 0.5 ms | |
Errors/accuracies | ||
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) | 0.02 % | |
Linearity error (relative to output range), (+/-) | 0.01 % | |
Crosstalk between the outputs, min. | 60 dB | |
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.01 % | |
Operational error limit in overall temperature range | ||
● Voltage, relative to output range, (+/-) | 0.1 % | |
Basic error limit (operational limit at 25 °C) | ||
● Voltage, relative to output range, (+/-) | 0.05 % | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | Yes | |
Interrupts/diagnostics/status information | ||
Substitute values connectable | Yes | |
Diagnostic messages | ||
● Diagnostic information readable | Yes | |
● Short-circuit | Yes | |
● Group error | Yes | |
Diagnostics indication LED | ||
● Group error SF (red) | Yes | |
Parameter | ||
Remark | 7 byte | |
Diagnostics short-circuit | Disable / enable | |
Output type/range | deactivated / 1 to 5 V / +/ -10 V / +/- 5 V | |
Group diagnostics | Disable / enable | |
Response to CPU/master STOP | Output current and de-energized/substitute a value/keep last value | |
Potential separation | ||
Potential separation analog outputs | ||
● between the channels | No | |
● between the channels and backplane bus | Yes | |
● Between the channels and load voltage L+ | Yes | |
Permissible potential difference | ||
between MANA and M internally (UISO) | 75 V DC/60 V AC | |
Isolation | ||
Isolation tested with | 500 V DC | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -25 °C; = Tmin | |
● max. | 60 °C; = Tmax | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 15 mm | |
Height | 81 mm | |
Depth | 52 mm | |
Weights | ||
Weight, approx. | 40 g | |
last modified: | 02/01/2017 |