Technická data
Název:
SIPLUS DP 4DI ET200S
Popis:
SIPLUS ET200S 4DI (1PU=5PCS) -25...+60 DGR C WITH CONFORMAL COATING BASED ON 6ES7131-4BD01-0AA0 . ELECTRONIC MODULE 24V DC WIDTH: 15 MM 5 PCS PER PACKAGING UNIT
Technické informace:
Supply voltage | ||
Rated value (DC) | ||
● 24 V DC | Yes; From power module | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Input current | ||
from supply voltage L+, max. | Dependent on encoder | |
from backplane bus 3.3 V DC, max. | 10 mA | |
Encoder supply | ||
Type of output voltage | min. L+ (-0.5 V), under load | |
Output current | ||
● Rated value | 500 mA | |
● permissible range | 0 to 500 mA | |
Power loss | ||
Power loss, typ. | 0.7 W | |
Address area | ||
Address space per module | ||
● with packing | 4 bit | |
● without packing | 1 byte | |
Digital inputs | ||
Number of digital inputs | 4 | |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes | |
Input voltage | ||
● Type of input voltage | DC | |
● Rated value (DC) | 24 V | |
● for signal "0" | -30 to +5V | |
● for signal "1" | +15 to +30V | |
Input current | ||
● for signal "1", typ. | 7 mA; at 24 V | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— parameterizable | No | |
— at "0" to "1", min. | 2 ms; typically 3 ms | |
— at "0" to "1", max. | 4.5 ms | |
— at "1" to "0", min. | 2 ms; typically 3 ms | |
— at "1" to "0", max. | 4.5 ms | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 600 m | |
Encoder | ||
Connectable encoders | ||
● 2-wire sensor | Yes | |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA | |
Interrupts/diagnostics/status information | ||
Diagnostic functions | No | |
Diagnostics indication LED | ||
● Group error SF (red) | No | |
● Status indicator digital input (green) | Yes; per channel | |
Parameter | ||
Remark | 1 byte | |
Potential separation | ||
Potential separation digital inputs | ||
● between the channels | No | |
● between the channels and backplane bus | Yes | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC | |
Isolation | ||
Isolation tested with | 500 V DC | |
Standards, approvals, certificates | ||
CE mark | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -25 °C; = Tmin | |
● max. | 60 °C; = Tmax | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 15 mm | |
Height | 81 mm | |
Depth | 52 mm | |
Weights | ||
Weight, approx. | 35 g | |
last modified: | 02/01/2017 |