Technická data
Název:
SIPLUS ET200S EM ET 1SI
Popis:
SIPLUS ET200S EM 1SI -25 ... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7138-4DF01-0AB0
Technické informace:
Supply voltage | ||
Rated value (DC) | 24 V | |
Reverse polarity protection | Yes | |
Input current | ||
from supply voltage L+, max. | 120 mA | |
from backplane bus 3.3 V DC, max. | 10 mA | |
Power loss | ||
Power loss, typ. | 1.2 W | |
Memory | ||
Standard blocks | 5 100 byte; S_SEND 2700, S_RCV 2400, S_XON 2600, S_RTS 2600, S_V24 2700, S_VSTAT 1800, S_VSET 1800 | |
Interfaces | ||
Number of interfaces | 1 | |
Interface physics, RS 232C (V.24) | Yes; RS 232C signals: 8 (TxD, RxD, RTS, CTS, DTR, DSR, DCD, PE) | |
Interface (physical) RS 422/485 (X.27) | Yes; RS-422 signals: 5 (TxD(A), RxD(A), TxD(B), RxD(B), PE); RS-485 signals: 3 (R/T(A), R/T(B), PE) | |
RS 232, cable length shielded, max. | 15 m | |
RS 422/RS 485, cable length shielded, max. | 1 200 m | |
Point-to-point | ||
Integrated protocol driver | ||
— 3964 (R) | Yes | |
— ASCII | Yes | |
Transmission rate, RS 422/485 | ||
— with 3964 (R) protocol, max. | 115.2 kbit/s; half duplex: 110, 300, 600, 1 200, 2 400, 4 800, 9 600, 19 200, 38 400, 57 600, 76 800, 115 200 bps | |
— with ASCII protocol, max. | 115.2 kbit/s; Full duplex: 110, 300, 600, 1 200, 2 400, 4 800, 9 600, 19 200, 38 400, 57 600, 76 800, 115 200 bps | |
Transmission speed, RS 232 | ||
— with 3964 (R) protocol, max. | 115.2 kbit/s; half duplex: 110, 300, 600, 1 200, 2 400, 4 800, 9 600, 19 200, 38 400, 57 600, 76 800, 115 200 bps | |
— with ASCII protocol, max. | 115.2 kbit/s; Full duplex: 110, 300, 600, 1 200, 2 400, 4 800, 9 600, 19 200, 38 400, 57 600, 76 800, 115 200 bps | |
Character frame (adjustable) | ||
— Bits per character | 7 or 8 | |
— Number of start/stop bits | 1 or 2 | |
— Bits per character frame | 10 | |
— Parity | none, odd, even, any | |
Data quantity per PLC sampling cycle | ||
— Send | 32 byte; with IM151-1 Standard as of 6ES7 151-1AA04-0AB0; with IM151-1 High Feature as of 6ES7 151-1BA01-0AB0; otherwise 8 bytes | |
— Receive | 32 byte; with IM151-1 Standard as of 6ES7 151-1AA04-0AB0; with IM151-1 High Feature as of 6ES7 151-1BA01-0AB0; otherwise 8 bytes | |
Interrupts/diagnostics/status information | ||
Diagnostics indication LED | ||
● Receive RxD (green) | Yes | |
● Transmit TxD (green) | Yes | |
● Group error SF (red) | Yes | |
Potential separation | ||
Potential separation interface | ||
● Between RS 422/485 and internal power supply | Yes | |
● between RS 232 and internal power supply | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -25 °C; = Tmin | |
● max. | 70 °C; = Tmax | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 15 mm | |
Height | 81 mm | |
Depth | 52 mm | |
Weights | ||
Weight, approx. | 50 g | |
last modified: | 02/01/2017 |