Technická data
Název:
SIPLUS_ET200S 2 AI RTD HF
Popis:
SIPLUS ET200S EM 2AI RTD HF -25 ... +60 DEGREES C BASED ON 6ES7134-4NB51-0AB0
Technické informace:
Supply voltage | ||
Load voltage L+ | ||
● Rated value (DC) | 24 V; From power module | |
● Reverse polarity protection | Yes | |
Input current | ||
from load voltage L+ (without load), max. | 30 mA | |
from backplane bus 3.3 V DC, max. | 10 mA | |
Power loss | ||
Power loss, typ. | 0.6 W | |
Address area | ||
Address space per module | ||
● Address space per module, max. | 4 byte | |
Analog inputs | ||
Number of analog inputs | 2 | |
permissible input voltage for voltage input (destruction limit), max. | 9 V | |
Constant measurement current for resistance-type transmitter, typ. | 1.25 mA | |
Cycle time (all channels) max. | Number of active channels per module x basic conversion time | |
Technical unit for temperature measurement adjustable | Yes | |
Input ranges | ||
● Voltage | Yes | |
● Current | No | |
● Thermocouple | Yes | |
● Resistance thermometer | Yes | |
● Resistance | Yes | |
Input ranges (rated values), resistance thermometer | ||
● Cu 10 | Yes | |
● Input resistance (Cu 10) | 10 MΩ | |
● Ni 100 | Yes | |
● Input resistance (Ni 100) | 10 MΩ | |
● Ni 1000 | Yes | |
● Input resistance (Ni 1000) | 10 MΩ | |
● Ni 120 | Yes | |
● Input resistance (Ni 120) | 10 MΩ | |
● Ni 200 | Yes | |
● Input resistance (Ni 200) | 10 MΩ | |
● Ni 500 | Yes | |
● Input resistance (Ni 500) | 10 MΩ | |
● Pt 100 | Yes | |
● Input resistance (Pt 100) | 10 MΩ | |
● Pt 1000 | Yes | |
● Input resistance (Pt 1000) | 10 MΩ | |
● Pt 200 | Yes | |
● Input resistance (Pt 200) | 10 MΩ | |
● Pt 500 | Yes | |
● Input resistance (Pt 500) | 10 MΩ | |
Input ranges (rated values), resistors | ||
● 0 to 150 ohms | Yes | |
● Input resistance (0 to 150 ohms) | 10 MΩ | |
● 0 to 300 ohms | Yes | |
● Input resistance (0 to 300 ohms) | 10 MΩ | |
● 0 to 600 ohms | Yes | |
● Input resistance (0 to 600 ohms) | 10 MΩ | |
● 0 to 3000 ohms | Yes | |
● Input resistance (0 to 3000 ohms) | 10 MΩ | |
Thermocouple (TC) | ||
Temperature compensation | ||
— internal temperature compensation | Yes | |
Characteristic linearization | ||
● parameterizable | Yes; for Ptxxx, Nixxx | |
— for resistance thermometer | Ptxxx, Nixxx | |
Cable length | ||
● shielded, max. | 200 m | |
Analog value generation for the inputs | ||
Measurement principle | integrating (Sigma-Delta) | |
Integration and conversion time/resolution per channel | ||
● Resolution with overrange (bit including sign), max. | 16 bit; for Pt100, Ni100, Ni120, Pt200, Ni200, Pt 500, Ni 500, Pt1000, Ni1000, Cu10: 15 bits + sign; for 150, 300, 600, 3000 ohms: 15 bits; for PTC: 1 bits | |
● Integration time (ms) | 16,7 / 20 ms | |
● Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz | |
● Conversion time (per channel) | Basic conversion time incl. integration time: 50 / 60 ms; additional conversion time for diagnostics of wire break test: 5 / 5 ms; additional conversion time for line compensation with 3-wire connection: 50 / 60 ms | |
Smoothing of measured values | ||
● parameterizable | Yes; In four stages by means of digital filtering | |
● Step: None | Yes; 1 x cycle time | |
● Step: low | Yes; 4 x cycle time | |
● Step: Medium | Yes; 32 x cycle time | |
● Step: High | Yes; 64 x cycle time | |
Encoder | ||
Connection of signal encoders | ||
● for resistance measurement with two-wire connection | Yes | |
● for resistance measurement with three-wire connection | Yes; internal compensation of the line resistances | |
● for resistance measurement with four-wire connection | Yes | |
Errors/accuracies | ||
Linearity error (relative to input range), (+/-) | 0.01 % | |
Temperature error (relative to input range), (+/-) | 0.0009 %/K | |
Crosstalk between the inputs, min. | -50 dB | |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % | |
Operational error limit in overall temperature range | ||
● Resistance thermometer, relative to input range, (+/-) | Resistance-type transmitter: +/-0.1%; Pt100, Pt200, Pt500, Pt1000 standard: +/-1.0 K; Pt100, Pt200, Pt500, Pt1000 climate: +/-0.25 K; Ni100, Ni120, Ni200, Ni500, Ni1000 standard and climate: +/-0.4 K; Cu10 +/-1.5 K | |
Basic error limit (operational limit at 25 °C) | ||
● Resistance thermometer, relative to input range, (+/-) | Resistance-type transmitter: +/-0.05%; Pt100, Pt200, Pt500, Pt1000 standard: +/-0.6 K; Pt100, Pt200, Pt500, Pt1000 climate: +/-0.13 K; Ni100, Ni120, Ni200, Ni500, Ni1000 standard and climate: +/-0.2 K; Cu10 +/-1 K | |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | ||
● Series mode interference (peak value of interference < rated value of input range), min. | 70 dB | |
● Common mode interference (USS < 2.5 V) , min. | 90 dB | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | No | |
Interrupts/diagnostics/status information | ||
Diagnostic messages | ||
● Wire-break | Yes | |
● Group error | Yes | |
● Overflow/underflow | Yes | |
Diagnostics indication LED | ||
● Group error SF (red) | Yes | |
Parameter | ||
Remark | 7 byte | |
Diagnostics wire break | Disable / enable | |
Measurement type/range | Deactivated/ 150 Ohm / 300 Ohm / 600 Ohm /Pt100/Pt200/Pt500/Pt1000 each standard or climate range / Ni100/Ni120/Ni200/Ni500/Ni1000 each standard or climate range / Cu10 each standard or climate range / PTC | |
Group diagnostics | Disable / enable | |
Overflow/underflow | Disable / enable | |
Potential separation | ||
Potential separation analog inputs | ||
● between the channels | No | |
● between the channels and backplane bus | Yes | |
● Between the channels and load voltage L+ | Yes | |
Permissible potential difference | ||
between MANA and M internally (UISO) | 75 V DC/60 V AC | |
Isolation | ||
Isolation tested with | 500 V DC | |
Standards, approvals, certificates | ||
CE mark | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -25 °C; = Tmin | |
● max. | 60 °C; = Tmax | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 15 mm | |
Height | 81 mm | |
Depth | 52 mm | |
Weights | ||
Weight, approx. | 40 g | |
last modified: | 02/01/2017 |