Technická data
Název:
SIPLUS_ET200S 2 AI TC HF
Popis:
SIPLUS ET200S EM 2AI TC HF 0 ... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7134-4NB01-0AB0 . 15 MM WIDE, 15 BIT + SIGN WITH INTERNAL TEMERATURE COMPENSATION
Technické informace:
Supply voltage | ||
Load voltage L+ | ||
● Rated value (DC) | 24 V; From power module | |
● Reverse polarity protection | Yes | |
Input current | ||
from load voltage L+ (without load), max. | 30 mA | |
from backplane bus 3.3 V DC, max. | 10 mA | |
Power loss | ||
Power loss, typ. | 0.6 W | |
Address area | ||
Address space per module | ||
● Address space per module, max. | 4 byte | |
Analog inputs | ||
Number of analog inputs | 2 | |
permissible input voltage for voltage input (destruction limit), max. | 20 V; +/-20 V, continuous | |
Cycle time (all channels) max. | Number of active channels per module x basic conversion time | |
Technical unit for temperature measurement adjustable | Yes; Celsius / Fahrenheit | |
Input ranges | ||
● Voltage | Yes | |
● Current | No | |
● Thermocouple | Yes | |
● Resistance thermometer | No | |
● Resistance | No | |
Input ranges (rated values), voltages | ||
● -80 mV to +80 mV | Yes | |
● Input resistance (-80 mV to +80 mV) | 1 MΩ | |
Input ranges (rated values), thermocouples | ||
● Type B | Yes | |
● Input resistance (Type B) | 1 MΩ | |
● Type C | Yes | |
● Input resistance (Type C) | 1 MΩ | |
● Type E | Yes | |
● Input resistance (Type E) | 1 MΩ | |
● Type J | Yes | |
● Input resistance (type J) | 1 MΩ | |
● Type K | Yes | |
● Input resistance (Type K) | 1 MΩ | |
● Type L | Yes | |
● Input resistance (Type L) | 1 MΩ | |
● Type N | Yes | |
● Input resistance (Type N) | 1 MΩ | |
● Type R | Yes | |
● Input resistance (Type R) | 1 MΩ | |
● Type S | Yes | |
● Input resistance (Type S) | 1 MΩ | |
● Type T | Yes | |
● Input resistance (Type T) | 1 MΩ | |
Thermocouple (TC) | ||
Temperature compensation | ||
— internal temperature compensation | Yes; possible with TM-E15S24-AT, TM-E15C24-AT | |
— external temperature compensation with compensations socket | Yes; one external compensating box per channel | |
Characteristic linearization | ||
● parameterizable | Yes | |
— for thermocouples | Type B, C, E, J, K, L, N, R, S, T to IEC 584 | |
Cable length | ||
● shielded, max. | 50 m | |
Analog value generation for the inputs | ||
Measurement principle | integrating | |
Integration and conversion time/resolution per channel | ||
● Resolution with overrange (bit including sign), max. | 16 bit | |
● Integration time (ms) | 16,7 / 20 ms | |
● Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz | |
● Conversion time (per channel) | 66 ms; 66 / 80 ms; additional conversion time for diagnostic wire break test | |
Smoothing of measured values | ||
● parameterizable | Yes; In four stages by means of digital filtering | |
● Step: None | Yes; 1 x cycle time | |
● Step: low | Yes; 4 x cycle time | |
● Step: Medium | Yes; 32 x cycle time | |
● Step: High | Yes; 64 x cycle time | |
Errors/accuracies | ||
Linearity error (relative to input range), (+/-) | 0.01 % | |
Temperature error (relative to input range), (+/-) | 0.005 %/K | |
Crosstalk between the inputs, min. | -50 dB | |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % | |
Operational error limit in overall temperature range | ||
● Voltage, relative to input range, (+/-) | 0.1 %; +/-1.5 K for thermocouples, +/-7 K for thermocouples type C,+/-2.5 K with static thermal state (ambient temperature change < 0.3 K/min) | |
Basic error limit (operational limit at 25 °C) | ||
● Voltage, relative to input range, (+/-) | 0.05 %; +/-1 K with thermocouples, +/-5 K with thermocouples type C, +/-1.5 K with static thermal state (ambient temperature change < 0.3 K/min) | |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | ||
● Series mode interference (peak value of interference < rated value of input range), min. | 70 dB | |
● Common mode interference (USS < 2.5 V) , min. | 90 dB | |
Interrupts/diagnostics/status information | ||
Diagnostic messages | ||
● Wire-break | Yes; only thermocouples | |
● Group error | Yes | |
● Overflow/underflow | Yes | |
Diagnostics indication LED | ||
● Group error SF (red) | Yes | |
Parameter | ||
Remark | 4 byte | |
Diagnostics wire break | Disable / enable (wire break is detected only in thermocouples) | |
Measurement type/range | Deactivated/ +/- 80 mV/ TC-EL Type T (Cu-CuNi)/ TC-EL Type K (NiCr-Ni)/ TC-EL Type B (PtRh-PtRh)/ TC-EL Type c (Wer-Wer) TC-EL Type N (NiCrSi-NiSi)/ TC-EL Type E (NiCr-CuNi)/ TC-EL Type R (PtRh-Pt)/ TC-EL Type S (PtRh-Pt)/ TC-EL Type J (Fe-Cu-Ni)/ TC | |
Group diagnostics | Disable / enable | |
Overflow/underflow | Disable / enable | |
Comparison point | none / yes, internal | |
Potential separation | ||
Potential separation analog inputs | ||
● between the channels | No | |
● between the channels and backplane bus | Yes | |
● Between the channels and load voltage L+ | Yes | |
Permissible potential difference | ||
Between the inputs and MANA (UCM) | 140 V DC/100 V AC | |
between MANA and M internally (UISO) | 75 V DC/60 V AC | |
Isolation | ||
Isolation tested with | 500 V DC | |
Standards, approvals, certificates | ||
CE mark | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | 0 °C; = Tmin | |
● max. | 70 °C; = Tmax | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 15 mm | |
Height | 81 mm | |
Depth | 52 mm | |
Weights | ||
Weight, approx. | 40 g | |
last modified: | 02/01/2017 |