Technická data
Název:
SIPLUS_ET200S_2 RO DC24...AC230V/5A NO
Popis:
SIPLUS ET200S EM 2RO DC24V-AC230V/5A -25 ... +70 DEGREES C BASED ON 6ES7132-4HB01-0AB0 5 PIECES PER PACKAGING UNIT . ELECTRON. MODULES FOR ET 200S, 2 DO RELAY 24V DC - 230V AC/5A,15 MM WIDTH FIRST-UP SIGNAL WITH LED SF (GROUP FAULT),
Technické informace:
Supply voltage | ||
Load voltage L+ | ||
● Rated value (DC) | 24 V; From power module | |
● Reverse polarity protection | Yes | |
Input current | ||
from load voltage L+ (without load), max. | 30 mA | |
from backplane bus 3.3 V DC, max. | 10 mA | |
Power loss | ||
Power loss, typ. | 0.6 W | |
Address area | ||
Address space per module | ||
● with packing | 2 bit | |
● without packing | 1 byte | |
Digital outputs | ||
Number of digital outputs | 2 | |
Short-circuit protection | No | |
Limitation of inductive shutdown voltage to | No | |
Controlling a digital input | Yes | |
Output current | ||
● for signal "1" rated value | 5 A | |
● for signal "1" minimum load current | 8 mA | |
Parallel switching of two outputs | ||
● for uprating | No | |
● for redundant control of a load | No | |
Switching frequency | ||
● with resistive load, max. | 2 Hz | |
● with inductive load, max. | 0.5 Hz | |
● on lamp load, max. | 2 Hz | |
Relay outputs | ||
Switching capacity of contacts | ||
— Thermal continuous current, max. | 5 A | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 600 m | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | No | |
Interrupts/diagnostics/status information | ||
Diagnostic functions | No | |
Substitute values connectable | Yes; 0/1 | |
Diagnostics indication LED | ||
● Status indicator digital output (green) | Yes | |
Parameter | ||
Remark | 3 byte | |
Response to CPU/master STOP | Substitute a value/keep last value | |
Potential separation | ||
Potential separation digital outputs | ||
● between the channels | Yes | |
● between the channels and backplane bus | Yes | |
● Between the channels and load voltage L+ | Yes | |
Isolation | ||
tested with | ||
● Channels against backplane bus and load voltage L+ | 1500 V AC | |
● Load voltage L+ against backplane bus | 500 V DC | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -25 °C; = Tmin | |
● max. | 70 °C; = Tmax | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 15 mm | |
Height | 81 mm | |
Depth | 52 mm | |
Weights | ||
Weight, approx. | 50 g | |
last modified: | 02/01/2017 |