Technická data
Název:
SIPLUS ET200S 4DO (1VE = 5 Stueck)
Popis:
SIPLUS ET200S EM 4DO STANDARD -25 ... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7132-4BD02-0AA0 . ELECTRONIC MODULE 24V/0.5A DC WIDTH: 15MM 5 PIECES PER PACKAGING UNIT
Technické informace:
Supply voltage | ||
Reverse voltage protection | Yes; when using the same load voltage as on the power module | |
Load voltage L+ | ||
● Rated value (DC) | 24 V; From power module | |
● Reverse polarity protection | Yes; polarity reversal can lead to the digital outputs being connected through | |
Input current | ||
from load voltage L+ (without load), max. | 10 mA; Per channel | |
from backplane bus 3.3 V DC, max. | 10 mA | |
Power loss | ||
Power loss, typ. | 0.8 W | |
Address area | ||
Address space per module | ||
● with packing | 4 bit | |
● without packing | 1 byte | |
Digital outputs | ||
Number of digital outputs | 4 | |
Short-circuit protection | Yes | |
● Response threshold, typ. | 1 to 1.5 A | |
Limitation of inductive shutdown voltage to | o.k. | |
Controlling a digital input | Yes | |
Switching capacity of the outputs | ||
● on lamp load, max. | 5 W | |
Load resistance range | ||
● lower limit | 48 Ω | |
● upper limit | 3 400 Ω | |
Output voltage | ||
● for signal "1", min. | L+ (-1 V) | |
Output current | ||
● for signal "1" rated value | 0.5 A | |
● for signal "1" permissible range, min. | 7 mA | |
● for signal "1" permissible range, max. | 600 mA | |
● for signal "0" residual current, max. | 0.3 mA | |
Output delay with resistive load | ||
● "0" to "1", max. | 45 µs; Typical value | |
● "1" to "0", max. | 90 µs; Typical value | |
Parallel switching of two outputs | ||
● for uprating | No | |
● for redundant control of a load | Yes; per module | |
Switching frequency | ||
● with resistive load, max. | 800 Hz | |
● with inductive load, max. | 2 Hz | |
● on lamp load, max. | 10 Hz | |
Total current of the outputs | ||
● Current per module, max. | 2 A | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 600 m | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | Yes | |
Interrupts/diagnostics/status information | ||
Diagnostic functions | No | |
Diagnostics indication LED | ||
● Status indicator digital output (green) | Yes | |
Parameter | ||
Remark | 1 byte | |
Potential separation | ||
Potential separation digital outputs | ||
● between the channels | No | |
● between the channels and backplane bus | Yes | |
Isolation | ||
Isolation tested with | 500 V DC | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -25 °C; = Tmin | |
● max. | 70 °C; = Tmax | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 15 mm | |
Height | 81 mm | |
Depth | 52 mm | |
Weights | ||
Weight, approx. | 40 g | |
last modified: | 02/01/2017 |