Technická data
Název:
SIPLUS ET200S IM151 HF
Popis:
SIPLUS ET200S IM151 HF -25 ... +60 DEGREES C BASED ON 6ES7151-1BA02-0AB0
Technické informace:
Supply voltage | ||
Mains buffering | ||
● Mains/voltage failure stored energy time | 20 ms | |
Input current | ||
from supply voltage 1L+, max. | 200 mA | |
Power loss | ||
Power loss, typ. | 3.3 W | |
Address area | ||
Addressing volume | ||
● Inputs | 244 byte | |
● Outputs | 244 byte | |
Interfaces | ||
Interface physics, RS 485 | Yes | |
PROFIBUS DP | ||
● Transmission rate, max. | 12 Mbit/s | |
● SYNC capability | Yes | |
● FREEZE capability | Yes | |
● Direct data exchange (slave-to-slave communication) | Yes | |
Protocols | ||
Supports protocol for PROFINET IO | No | |
PROFIBUS DP | Yes | |
Protocols (Ethernet) | ||
● TCP/IP | No | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | Yes | |
Interrupts/diagnostics/status information | ||
Alarms | Yes | |
Diagnostic functions | Yes | |
Diagnostics indication LED | ||
● Bus fault BF (red) | Yes | |
● Group error SF (red) | Yes | |
● Monitoring 24 V voltage supply ON (green) | Yes | |
Potential separation | ||
between backplane bus and electronics | No | |
between electronic block and PROFIBUS DP | Yes | |
between supply voltage and electronics | No | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC | |
Isolation | ||
Isolation tested with | 500 V DC | |
Standards, approvals, certificates | ||
CE mark | Yes | |
UL approval | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -25 °C; = Tmin | |
● max. | 60 °C; = Tmax | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 45 mm | |
Height | 119.5 mm | |
Depth | 75 mm | |
Weights | ||
Weight, approx. | 150 g | |
last modified: | 02/01/2017 |