Technická data
Název:
SIPLUS ET 200SP DI 8x24VDC HF
Popis:
SIPLUS ET 200SP DI 8x24VDC HF -40...+70°C mit conformal coating BasedOn: 6ES7131-6BF00-0CA0 . digital input module, Di 8x 24VDC high feature, fits to BU-TYPE A0, color code CC01, channel diagnosis
Technické informace:
General information | ||
Firmware version | V2.0 | |
● FW update possible | Yes | |
usable BaseUnits | BU type A0 | |
Color code for module-specific color identification plate | CC01 | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
Engineering with | ||
● PROFIBUS as of GSD version/GSD revision | GSD Revision 5 | |
● PROFINET as of GSD version/GSD revision | GSDML V2.3 | |
Operating mode | ||
● DI | Yes | |
● Counter | No | |
● Oversampling | No | |
● MSI | Yes | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Encoder supply | ||
24 V encoder supply | ||
● 24 V | Yes | |
● Short-circuit protection | Yes; per channel, electronic | |
● Output current, max. | 700 mA; Per channel | |
Power loss | ||
Power loss, typ. | 1.5 W | |
Address area | ||
Address space per module | ||
● Address space per module, max. | 8 byte; 2 channels per submodule + QI information | |
Hardware configuration | ||
Submodules | ||
● Number of configurable submodules, max. | 4 | |
Selection of BaseUnit for connection variants | ||
● 1-wire connection | BU type A0 | |
● 2-wire connection | BU type A0 | |
● 3-wire connection | BU type A0 with AUX terminals | |
● 4-wire connection | BU type A0 + external terminals | |
Digital inputs | ||
Number of digital inputs | 8 | |
Source/sink input | P-reading | |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes | |
Input characteristic curve in accordance with IEC 61131, type 2 | No | |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes | |
Pulse extension | Yes; Pulse duration from 4 µs | |
● Length | 2 s; 50 ms, 100 ms, 200 ms, 500 ms, 1 s, 2 s | |
Edge evaluation | Yes; rising edge, falling edge, edge change | |
Input voltage | ||
● Type of input voltage | DC | |
● Rated value (DC) | 24 V | |
● for signal "0" | -30 to +5V | |
● for signal "1" | +11 to +30V | |
Input current | ||
● for signal "1", typ. | 2.5 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— parameterizable | Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 µs, depending on line length) | |
for interrupt inputs | ||
— parameterizable | Yes | |
for counter/technological functions | ||
— parameterizable | No | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 600 m | |
Encoder | ||
Connectable encoders | ||
● 2-wire sensor | Yes | |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | Yes | |
Filtering and processing time (TCI), min. | 420 µs | |
Bus cycle time (TDP), min. | 500 µs | |
Jitter, max. | 8 µs | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Alarms | ||
● Diagnostic alarm | Yes; channel by channel | |
● Hardware interrupt | Yes; Parameterizable, channels 0 to 7 | |
Diagnostic messages | ||
● Diagnostic information readable | Yes | |
● Monitoring the supply voltage | Yes | |
— parameterizable | Yes | |
● Monitoring of encoder power supply | Yes; channel by channel | |
● Wire-break | Yes; channel by channel | |
● Short-circuit | Yes; channel by channel | |
Diagnostics indication LED | ||
● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | Yes; Red LED | |
● for module diagnostics | Yes; green/red DIAG LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | No | |
● between the channels and backplane bus | Yes | |
● between the channels and the power supply of the electronics | No | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin | |
● horizontal installation, max. | 70 °C; = Tmax; > +60 °C encoder supply output current max. 350 mA per channel | |
Relative humidity | ||
● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Dimensions | ||
Width | 15 mm | |
Height | 73 mm | |
Depth | 58 mm | |
Weights | ||
Weight, approx. | 28 g | |
last modified: | 09/25/2017 |