Technická data
Název:
SIPLUS ET 200SP DI 8XNAMUR HF
Popis:
SIPLUS ET 200SP -40...+70 GRAD C WITH CONFORMAL COATING STARTUP TEMP.: -25 DEGREE C BASEDON 6ES7131-6TF00-0CA0 . DIGITAL INPUT MODULE, DI 8X NAMUR HIGH FEATURE, FITS TO BU-TYPE A0, COLOR CODE CC01, CHANNEL DIAGNOSIS
Technické informace:
General information | ||
Product type designation | DI 8xNAMUR HF | |
Firmware version | V1.0 | |
● FW update possible | Yes | |
usable BaseUnits | BU type A0 | |
Color code for module-specific color identification plate | CC01 | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated as of version | V13 / V13 | |
● STEP 7 configurable/integrated as of version | V5.5 SP3 / - | |
● PROFIBUS as of GSD version/GSD revision | GSD Revision 5 | |
● PROFINET as of GSD version/GSD revision | GSDML V2.3 | |
Operating mode | ||
● DI | Yes | |
● Counter | No | |
● Oversampling | No | |
● MSI | No | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Encoder supply | ||
Number of outputs | 8 | |
Short-circuit protection | Yes | |
24 V encoder supply | ||
● 24 V | No | |
● Short-circuit protection | No | |
Power loss | ||
Power loss, typ. | 1.5 W | |
Address area | ||
Address space per module | ||
● Address space per module, max. | 1 byte; + 1 byte for QI information | |
Digital inputs | ||
Number of digital inputs | 8 | |
Digital inputs, parameterizable | Yes | |
Type | NAMUR | |
Pulse extension | Yes; 0.5 s, 1 s, 2 s | |
Edge evaluation | Yes; rising edge, falling edge, edge change | |
Signal change flutter | Yes; 2 to 32 signal changes | |
Flutter observation window | Yes; 0.5 s, 1 s to 100 s in 1-s steps | |
Input voltage | ||
● Type of input voltage | DC | |
● Rated value (DC) | 8.2 V | |
Input current | ||
for 10 k switched contact | ||
— for signal "0" | 0.35 to 1.2 mA | |
— for signal "1" | 2.1 to 7 mA | |
for unswitched contact | ||
— for signal "0", max. (permissible quiescent current) | 0.5 mA | |
— for signal "1" | typ. 8 mA | |
for NAMUR encoders | ||
— for signal "0" | 0.35 to 1.2 mA | |
— for signal "1" | 2.1 to 7 mA | |
Input delay (for rated value of input voltage) | ||
● tolerated changeover time for changeover contacts | 300 ms | |
for standard inputs | ||
— parameterizable | No | |
for NAMUR inputs | ||
— at "0" to "1", max. | 12 ms | |
— at "1" to "0", max. | 12 ms | |
Cable length | ||
● shielded, max. | 200 m | |
Encoder | ||
Connectable encoders | ||
● NAMUR encoder/changeover contact according to EN 60947 | Yes | |
● Single contact / changeover contact unconnected | Yes | |
● Single contact / changeover contact connected with 10 kΩ | Yes | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | No | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Alarms | ||
● Diagnostic alarm | Yes; channel by channel | |
● Hardware interrupt | Yes; Parameterizable, channels 0 to 7 | |
Diagnostic messages | ||
● Diagnostic information readable | Yes | |
● Monitoring the supply voltage | Yes | |
— parameterizable | Yes | |
● Monitoring of encoder power supply | Yes; channel by channel | |
● Wire-break | Yes; channel by channel | |
● Short-circuit | Yes; channel by channel | |
● Group error | Yes | |
Diagnostics indication LED | ||
● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | Yes; Red LED | |
● for module diagnostics | Yes; green/red DIAG LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | No | |
● between the channels and backplane bus | Yes | |
● between the channels and the power supply of the electronics | Yes | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC (base isolation) | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin; Startup @ -25 °C | |
● horizontal installation, max. | 70 °C; = Tmax; > +60 °C number of simultaneously controllable inputs max. 4 (no adjacent points) | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 15 mm | |
Weights | ||
Weight, approx. | 32 g | |
last modified: | 02/01/2017 |