Technická data
Název:
SIPLUS ET 200SP DQ 4X24VDC/2A HF
Popis:
SIPLUS ET 200SP DQ 4X24VDC/2A -40 ... +70 °C with conformal coating BasedOn:6ES7132-6BD20-0CA0 . digital output module, fits to BU-TYPE A0, color code CC02, channel diagnosis
Technické informace:
General information | ||
Firmware version | V1.0 | |
● FW update possible | Yes | |
usable BaseUnits | BU type A0 | |
Color code for module-specific color identification plate | CC02 | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
Engineering with | ||
● PROFIBUS as of GSD version/GSD revision | GSD Revision 5 | |
● PROFINET as of GSD version/GSD revision | GSDML V2.3 | |
Operating mode | ||
● Oversampling | No | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Input current | ||
Current consumption, max. | 60 mA; without load | |
Power loss | ||
Power loss, typ. | 1 W | |
Address area | ||
Address space per module | ||
● Address space per module, max. | 1 byte; + 1 byte for QI information | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | Yes | |
Bus cycle time (TDP), min. | 500 µs | |
Jitter, max. | 8 µs | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Substitute values connectable | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
Diagnostic messages | ||
● Monitoring the supply voltage | Yes | |
● Wire-break | Yes; channel by channel | |
● Short-circuit | Yes; channel by channel | |
● Group error | Yes | |
Diagnostics indication LED | ||
● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | Yes; Red LED | |
● for module diagnostics | Yes; green/red DIAG LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | No | |
● between the channels and backplane bus | Yes | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin | |
● horizontal installation, max. | 70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C max. total current 1 A | |
Altitude during operation based on sea level | ||
● Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Dimensions | ||
Width | 15 mm | |
Height | 73 mm | |
Depth | 58 mm | |
Weights | ||
Weight, approx. | 30 g | |
last modified: | 09/25/2017 |