Technická data
Název:
SIPLUS ET 200SP DQ 8X24VDC/0,5A HF
Popis:
SIPLUS ET 200SP -40...+70 GRAD C STARTUP TEMP.: -25 DEGREE C WITH CONFORMAL COATING BASEDON 6ES7132-6BF00-0CA0 . DIGITAL OUTPUT MODULE, DQ 8X24VDC/0,5A HIGH FEATURE, FITS TO BU-TYPE A0, COLOR CODE CC02, CHANNEL DIAGNOSIS
Technické informace:
General information | ||
Product type designation | DQ 8x24VDC/0.5A HF | |
Firmware version | V1.2 | |
● FW update possible | Yes | |
usable BaseUnits | BU type A0 | |
Color code for module-specific color identification plate | CC02 | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated as of version | V13 / V13 | |
● STEP 7 configurable/integrated as of version | V5.5 SP3 / - | |
● PCS 7 configurable/integrated as of version | V8.1 SP1 | |
● PROFIBUS as of GSD version/GSD revision | GSD Revision 5 | |
● PROFINET as of GSD version/GSD revision | GSDML V2.3 | |
Operating mode | ||
● DQ | Yes | |
● DQ with energy-saving function | No | |
● PWM | No | |
● Oversampling | No | |
● MSO | Yes | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Input current | ||
Current consumption, max. | 45 mA; without load | |
Output voltage | ||
Rated value (DC) | 24 V | |
Power loss | ||
Power loss, typ. | 1 W | |
Address area | ||
Address space per module | ||
● Address space per module, max. | 1 byte; + 1 byte for QI information | |
Digital outputs | ||
Number of digital outputs | 8 | |
Current-sinking | No | |
Current-sourcing | Yes | |
Short-circuit protection | ||
● Response threshold, typ. | 0.7 to 1.3 A | |
Limitation of inductive shutdown voltage to | Typ. L+ (-50 V) | |
Controlling a digital input | Yes | |
Switching capacity of the outputs | ||
● with resistive load, max. | 0.5 A | |
● on lamp load, max. | 5 W | |
Load resistance range | ||
● lower limit | 48 Ω | |
● upper limit | 12 kΩ | |
Output current | ||
● for signal "1" rated value | 0.5 A | |
● for signal "0" residual current, max. | 0.1 mA | |
Output delay with resistive load | ||
● "0" to "1", typ. | 50 µs | |
● "1" to "0", typ. | 100 µs | |
Parallel switching of two outputs | ||
● for uprating | No | |
● for redundant control of a load | Yes | |
Switching frequency | ||
● with resistive load, max. | 100 Hz | |
● with inductive load, max. | 2 Hz | |
● on lamp load, max. | 10 Hz | |
Total current of the outputs | ||
● Current per channel, max. | 0.5 A | |
● Current per module, max. | 4 A | |
Total current of the outputs (per module) | ||
horizontal installation | ||
— up to 60 °C, max. | 4 A | |
vertical installation | ||
— up to 60 °C, max. | 4 A | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 600 m | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | Yes | |
Execution and activation time (TCO), min. | 48 µs | |
Bus cycle time (TDP), min. | 500 µs | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Substitute values connectable | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
Diagnostic messages | ||
● Monitoring the supply voltage | Yes | |
● Wire-break | Yes; channel by channel | |
● Short-circuit | Yes; channel by channel | |
● Group error | Yes | |
Diagnostics indication LED | ||
● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | Yes; Red LED | |
● for module diagnostics | Yes; green/red DIAG LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | No | |
● between the channels and backplane bus | Yes | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC (base isolation) | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin; Startup @ -25 °C | |
● horizontal installation, max. | 70 °C; = Tmax; > +60 °C max. total current 1.0 A | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 15 mm | |
Weights | ||
Weight, approx. | 30 g | |
last modified: | 02/01/2017 |