Technická data
Název:
SIPLUS ET 200SP RQ 4X24VDC/2A CO ST
Popis:
SIPLUS ET 200SP -40...+60 DEGREE C STARTUP TEMP.: -25 DEGREE C WITH CONFORMAL COATING BASEDON 6ES7132-6GD50-0BA0 . SIGNAL RELAY CHANGE OVER, RQ 4X24VDC/2A CO ST, FITS TO BU-TYPE A0, COLOR CODE CC00, MODULE DIAGNOSIS
Technické informace:
General information | ||
Product type designation | RQ 4x24VUC/2A CO ST | |
Firmware version | V1.0 | |
● FW update possible | Yes | |
usable BaseUnits | BU type A0 | |
Color code for module-specific color identification plate | CC00 | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated as of version | V13 / V13 | |
● STEP 7 configurable/integrated as of version | V5.5 SP3 / - | |
● PROFIBUS as of GSD version/GSD revision | GSD Revision 5 | |
● PROFINET as of GSD version/GSD revision | GSDML V2.3 | |
Operating mode | ||
● DQ | Yes | |
● DQ with energy-saving function | No | |
● PWM | No | |
● Oversampling | No | |
● MSO | No | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Input current | ||
Current consumption (rated value) | 50 mA | |
Power loss | ||
Power loss, typ. | 1.2 W | |
Address area | ||
Address space per module | ||
● Address space per module, max. | 1 byte; + 1 byte for QI information | |
● Inputs | 1 byte; With QI | |
● Outputs | 1 byte | |
Digital outputs | ||
Number of digital outputs | 4 | |
Short-circuit protection | No | |
Switching frequency | ||
● with resistive load, max. | 2 Hz | |
Total current of the outputs | ||
● Current per channel, max. | 2 A | |
● Current per module, max. | 8 A | |
Total current of the outputs (per module) | ||
horizontal installation | ||
— up to 60 °C, max. | 8 A | |
vertical installation | ||
— up to 60 °C, max. | 8 A | |
Relay outputs | ||
● Number of relay outputs | 4 | |
● Rated supply voltage of relay coil L+ (DC) | 24 V | |
● Current consumption of relays (coil current of all relays), max. | 40 mA | |
Switching capacity of contacts | ||
— with resistive load, max. | 2 A | |
— Thermal continuous current, max. | 2 A | |
— Switching current, min. | 1 mA; 5 V DC | |
— Rated switching voltage (DC) | 24 V | |
— Rated switching voltage (AC) | 24 V | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 200 m | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | No | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Substitute values connectable | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
Diagnostic messages | ||
● Monitoring the supply voltage | Yes | |
● Wire-break | No | |
● Short-circuit | No | |
● Group error | Yes | |
Diagnostics indication LED | ||
● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | No | |
● for module diagnostics | Yes; green/red DIAG LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | Yes | |
● between the channels and backplane bus | Yes | |
● between the channels and the power supply of the electronics | Yes | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC (base isolation) | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin; Startup @ -25 °C | |
● horizontal installation, max. | 60 °C; = Tmax | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 15 mm | |
Weights | ||
Weight, approx. | 30 g | |
last modified: | 02/01/2017 |