Technická data
Název:
SIPLUS ET 200SP AI 8xU BASIC
Popis:
SIPLUS ET 200SP AI 8xU BASIC -40 ... +60 °C with conformal coating BasedOn: 6ES7134-6FF00-0AA1 . AI 8XU BASIC, FITS TO BU-TYPE A0, A1, Color Code CC02, Module Diagnosis, 16BIT
Technické informace:
General information | ||
Firmware version | ||
● FW update possible | Yes | |
usable BaseUnits | BU type A0, A1 | |
Color code for module-specific color identification plate | CC02 | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
● Measuring range scalable | No | |
Engineering with | ||
● PROFIBUS as of GSD version/GSD revision | GSD Revision 5 | |
● PROFINET as of GSD version/GSD revision | GSDML V2.3 | |
Operating mode | ||
● Oversampling | No | |
● MSI | No | |
CiR – Configuration in RUN | ||
Reparameterization possible in RUN | Yes | |
Calibration possible in RUN | No | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Input current | ||
Current consumption, max. | 25 mA | |
Power loss | ||
Power loss, typ. | 0.7 W | |
Address area | ||
Address space per module | ||
● Address space per module, max. | 16 byte | |
Analog inputs | ||
Number of analog inputs | 8; Single-ended | |
permissible input voltage for voltage input (destruction limit), max. | 30 V | |
Cycle time (all channels), min. | 1 ms; per channel | |
Input ranges (rated values), voltages | ||
● 0 to +10 V | Yes; 15 bit | |
● Input resistance (0 to 10 V) | 100 kΩ | |
● -10 V to +10 V | Yes; 16 bit incl. sign | |
● Input resistance (-10 V to +10 V) | 100 kΩ | |
Cable length | ||
● shielded, max. | 200 m | |
Analog value generation for the inputs | ||
Integration and conversion time/resolution per channel | ||
● Resolution with overrange (bit including sign), max. | 16 bit | |
● Integration time, parameterizable | Yes | |
● Interference voltage suppression for interference frequency f1 in Hz | 16.67 / 50 / 60 / 4 800 (16.67 / 50 / 60) | |
● Conversion time (per channel) | 180 / 60 / 50 / 0.625 (67.5 / 22.5 / 18.75) ms | |
Smoothing of measured values | ||
● Number of smoothing levels | 4; None; 4/8/16 times | |
● parameterizable | Yes | |
Encoder | ||
Connection of signal encoders | ||
● for voltage measurement | Yes | |
● for current measurement as 4-wire transducer | No | |
Errors/accuracies | ||
Linearity error (relative to input range), (+/-) | 0.02 % | |
Temperature error (relative to input range), (+/-) | 0.009 %/K | |
Crosstalk between the inputs, min. | -50 dB | |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % | |
Operational error limit in overall temperature range | ||
● Voltage, relative to input range, (+/-) | 0.9 % | |
Basic error limit (operational limit at 25 °C) | ||
● Voltage, relative to input range, (+/-) | 0.3 % | |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | ||
● Series mode interference (peak value of interference < rated value of input range), min. | 70 dB; With conversion time 67.5 / 22.5 / 18.75 ms: 40 dB | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | No | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
● Limit value alarm | No | |
Diagnostic messages | ||
● Monitoring the supply voltage | Yes | |
● Wire-break | No | |
● Short-circuit | No | |
● Group error | Yes | |
● Overflow/underflow | Yes | |
Diagnostics indication LED | ||
● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | No | |
● for module diagnostics | Yes; green/red DIAG LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | No | |
● between the channels and backplane bus | Yes | |
● between the channels and the power supply of the electronics | No | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin | |
● horizontal installation, max. | 60 °C; = Tmax | |
Relative humidity | ||
● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Dimensions | ||
Width | 15 mm | |
Weights | ||
Weight, approx. | 31 g | |