Technická data
Název:
SIPLUS ET 200SP AI 2 X U/I 2-, 4-WIRE HF
Popis:
SIPLUS ET 200SP -40 ... +60 GRAD C STARTUP TEMP.: -25 DEGREE C WITH CONFORMAL COATING BASEDON 6ES7134-6HB00-0CA1 . ANALOG INPUT MODULE, AI 2X U/I 2-,4-WIRE HIGH FEAT., FITS TO BU-TYPE A0, A1, COLOR CODE CC05, CHANNEL DIAGNOSIS, 16BIT, +/-0,1%
Technické informace:
General information | ||
Product type designation | AI 2xU/I 2-/4-wire HF | |
Firmware version | V1.0 | |
● FW update possible | Yes | |
usable BaseUnits | BU type A0, A1 | |
Color code for module-specific color identification plate | CC03 | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
● Measuring range scalable | No | |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated as of version | V13 | |
● STEP 7 configurable/integrated as of version | V5.5 SP3 / - | |
● PCS 7 configurable/integrated as of version | V8.1 SP1 | |
● PROFIBUS as of GSD version/GSD revision | GSD Revision 5 | |
● PROFINET as of GSD version/GSD revision | GSDML V2.3 | |
Operating mode | ||
● Oversampling | No | |
● MSI | No | |
CiR – Configuration in RUN | ||
Reparameterization possible in RUN | Yes | |
Calibration possible in RUN | Yes | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Input current | ||
Current consumption (rated value) | 39 mA; without sensor supply | |
Encoder supply | ||
24 V encoder supply | ||
● 24 V | Yes | |
● Short-circuit protection | Yes | |
● Output current, max. | 20 mA; max. 50 mA per channel for a duration < 10 s (two-wire) | |
Additional 24 V encoder supply | ||
● Output current, max. | 100 mA; max. 150 mA for a duration of < 10 s (four-wire) | |
Power loss | ||
Power loss, typ. | 0.95 W; without sensor supply | |
Address area | ||
Address space per module | ||
● Address space per module, max. | 4 byte; + 1 byte for QI information | |
Analog inputs | ||
Number of analog inputs | 2; Differential inputs | |
permissible input voltage for voltage input (destruction limit), max. | 30 V | |
permissible input current for current input (destruction limit), max. | 50 mA | |
Input ranges (rated values), voltages | ||
● 0 to +10 V | Yes; 15 bit | |
● Input resistance (0 to 10 V) | 75 kΩ | |
● 1 V to 5 V | Yes; 15 bit | |
● Input resistance (1 V to 5 V) | 75 kΩ | |
● -10 V to +10 V | Yes; 16 bit incl. sign | |
● Input resistance (-10 V to +10 V) | 75 kΩ | |
● -5 V to +5 V | Yes; 16 bit incl. sign | |
● Input resistance (-5 V to +5 V) | 75 kΩ | |
Input ranges (rated values), currents | ||
● 0 to 20 mA | Yes; 15 bit | |
● Input resistance (0 to 20 mA) | 130 Ω | |
● -20 mA to +20 mA | Yes; 16 bit incl. sign | |
● Input resistance (-20 mA to +20 mA) | 130 Ω | |
● 4 mA to 20 mA | Yes; 15 bit | |
● Input resistance (4 mA to 20 mA) | 130 Ω | |
Cable length | ||
● shielded, max. | 1 000 m; 200 m for voltage measurement | |
Analog value generation for the inputs | ||
Measurement principle | Sigma Delta | |
Integration and conversion time/resolution per channel | ||
● Resolution with overrange (bit including sign), max. | 16 bit | |
● Integration time, parameterizable | Yes | |
● Interference voltage suppression for interference frequency f1 in Hz | 16.6 / 50 / 60 / 300 / 600 / 1 200 / 2 400 / 4 800 | |
● Basic execution time of the module (all channels released) | 1 ms | |
Smoothing of measured values | ||
● Number of smoothing levels | 6; none; 2-/4-/8-/16-/32-fold | |
● parameterizable | Yes | |
Encoder | ||
Connection of signal encoders | ||
● for voltage measurement | Yes | |
● for current measurement as 2-wire transducer | Yes | |
— Burden of 2-wire transmitter, max. | 650 Ω | |
● for current measurement as 4-wire transducer | Yes | |
Errors/accuracies | ||
Linearity error (relative to input range), (+/-) | 0.02 % | |
Temperature error (relative to input range), (+/-) | 0.005 %/K | |
Crosstalk between the inputs, min. | -50 dB | |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.01 % | |
Operational error limit in overall temperature range | ||
● Voltage, relative to input range, (+/-) | 0.2 % | |
● Current, relative to input range, (+/-) | 0.2 % | |
Basic error limit (operational limit at 25 °C) | ||
● Voltage, relative to input range, (+/-) | 0.05 %; 0.1 % at SFU 4.8 kHz | |
● Current, relative to input range, (+/-) | 0.05 %; 0.1 % at SFU 4.8 kHz | |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | ||
● Common mode voltage, max. | 35 V | |
● Common mode interference, min. | 90 dB | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | Yes | |
Filtering and processing time (TCI), min. | 800 µs | |
Bus cycle time (TDP), min. | 1 ms | |
Jitter, max. | 5 µs | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
● Limit value alarm | Yes; two upper and two lower limit values in each case | |
Diagnostic messages | ||
● Monitoring the supply voltage | Yes | |
● Wire-break | Yes; Measuring range 4 to 20 mA only | |
● Short-circuit | Yes; For 1 to 5 V or for current measuring ranges short-circuit in encoder supply | |
● Group error | Yes | |
● Overflow/underflow | Yes | |
Diagnostics indication LED | ||
● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | Yes; Red LED | |
● for module diagnostics | Yes; green/red DIAG LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | Yes | |
● between the channels and backplane bus | Yes | |
● between the channels and the power supply of the electronics | Yes | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC (base isolation) | |
between the inputs (UCM) | 75 V DC/60 V AC | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin; Startup @ -25 °C | |
● horizontal installation, max. | 60 °C; = Tmax | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 15 mm | |
Weights | ||
Weight, approx. | 32 g | |
last modified: | 02/01/2017 |