Technická data
Název:
SIPLUS ET 200SP AQ 2xI STANDARD
Popis:
SIPLUS ET 200SP AQ 2xI STANDARD -40 ... +70 GRAD C with conformal coating BasedOn: 6ES7135-6GB00-0BA1 . ANALOG OUTPUT MODULE, AQ 2XI STANDARD, PACKING UNIT: 1 PIECE, FITS TO BU-TYPE A0, A1, COLOR CODE CC00, MODULE DIAGNOSIS, 16 BIT
Technické informace:
General information | ||
Firmware version | ||
● FW update possible | Yes | |
usable BaseUnits | BU type A0, A1 | |
Color code for module-specific color identification plate | CC00 | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
● Output range scalable | No | |
Engineering with | ||
● PROFIBUS as of GSD version/GSD revision | GSD Revision 5 | |
● PROFINET as of GSD version/GSD revision | GSDML V2.3 | |
Operating mode | ||
● Oversampling | No | |
● MSO | No | |
CiR – Configuration in RUN | ||
Reparameterization possible in RUN | Yes | |
Calibration possible in RUN | No | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Input current | ||
Current consumption, max. | 110 mA | |
Power loss | ||
Power loss, typ. | 1.5 W | |
Address area | ||
Address space per module | ||
● Address space per module, max. | 4 byte; + 1 byte for QI information | |
Analog outputs | ||
Number of analog outputs | 2 | |
Cycle time (all channels), min. | 1 ms | |
Analog output with oversampling | No | |
Output ranges, current | ||
● 0 to 20 mA | Yes; 15 bit | |
● -20 mA to +20 mA | Yes; 16 bit incl. sign | |
● 4 mA to 20 mA | Yes; 14 bit | |
Connection of actuators | ||
● for current output two-wire connection | Yes | |
Load impedance (in rated range of output) | ||
● with current outputs, max. | 500 Ω | |
● with current outputs, inductive load, max. | 1 mH | |
Destruction limits against externally applied voltages and currents | ||
● Voltages at the outputs | 30 V | |
Cable length | ||
● shielded, max. | 1 000 m | |
Analog value generation for the outputs | ||
Settling time | ||
● for resistive load | 0.1 ms; Typical value | |
● for inductive load | 0.5 ms | |
Errors/accuracies | ||
Linearity error (relative to output range), (+/-) | 0.06 % | |
Temperature error (relative to output range), (+/-) | 0.01 %/K | |
Crosstalk between the outputs, min. | -50 dB | |
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.05 % | |
Operational error limit in overall temperature range | ||
● Current, relative to output range, (+/-) | 1 % | |
Basic error limit (operational limit at 25 °C) | ||
● Current, relative to output range, (+/-) | 0.3 % | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | No | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Substitute values connectable | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
Diagnostic messages | ||
● Monitoring the supply voltage | Yes | |
● Wire-break | Yes | |
● Group error | Yes | |
● Overflow/underflow | Yes | |
Diagnostics indication LED | ||
● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | No | |
● for module diagnostics | Yes; green/red DIAG LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | No | |
● between the channels and backplane bus | Yes | |
● between the channels and the power supply of the electronics | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin | |
● horizontal installation, max. | 70 °C; = Tmax | |
Relative humidity | ||
● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Dimensions | ||
Width | 15 mm | |
Height | 73 mm | |
Depth | 58 mm | |
Weights | ||
Weight, approx. | 31 g | |
last modified: | 09/25/2017 |