Technická data
Název:
SIPLUS ET 200SP F-DI 4/8x24VDC HF
Popis:
SIPLUS ET 200SP -25 ... +60 DEGREE WITH CONFORMAL COATING BASEDON 6ES7136-6BA00-0CA0 . ELECTRONIC MODULE 8 F-DI, PROFISAFE, 24V DC, 15 MM WIDTH, UP TO PL E (ISO 13849-1), SIL3 (IEC 61508)
Technické informace:
General information | ||
Product type designation | F-DI 8x24VDC HF | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated as of version | V12 | |
● STEP 7 configurable/integrated as of version | V5.5 SP3 / - | |
● PROFINET as of GSD version/GSD revision | V2.31 | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Input current | ||
Current consumption (rated value) | 75 mA; without load | |
Current consumption, max. | 21 mA; From the backplane bus | |
Encoder supply | ||
Number of outputs | 8 | |
Short-circuit protection | Yes; Electronic (response threshold 0.7 A to 1.8 A) | |
Output current | ||
● up to 60 °C, max. | 0.3 A | |
24 V encoder supply | ||
● 24 V | Yes; min. L+ (-1.5 V) | |
● Short-circuit protection | Yes | |
● Output current, max. | 800 mA; Total current of all encoders | |
Power | ||
Power available from the backplane bus | 70 mW | |
Power loss | ||
Power loss, typ. | 4 W | |
Address area | ||
Address space per module | ||
● Inputs | 6 byte | |
● Outputs | 4 byte | |
Digital inputs | ||
Number of digital inputs | 8 | |
Source/sink input | Yes; P-reading | |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes | |
Input voltage | ||
● Type of input voltage | DC | |
● Rated value (DC) | 24 V | |
● for signal "0" | -30 to +5V | |
● for signal "1" | +15 to +30V | |
Input current | ||
● for signal "1", typ. | 3.7 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— parameterizable | Yes | |
— at "0" to "1", min. | 0.4 ms | |
— at "0" to "1", max. | 20 ms | |
— at "1" to "0", min. | 0.4 ms | |
— at "1" to "0", max. | 20 ms | |
for counter/technological functions | ||
— parameterizable | No | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 500 m | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes, "Alarms/diagnostic messages" section in the manual | |
Alarms | ||
● Diagnostic alarm | Yes | |
● Hardware interrupt | No | |
Diagnostics indication LED | ||
● RUN LED | Yes; Green LED | |
● ERROR LED | Yes; Red LED | |
● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | Yes; Red LED | |
● for module diagnostics | Yes; green/red DIAG LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | No | |
● between the channels and backplane bus | Yes | |
● between the channels and the power supply of the electronics | No | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -25 °C | |
● horizontal installation, max. | 60 °C | |
● vertical installation, min. | -25 °C | |
● vertical installation, max. | 50 °C | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 15 mm | |
Weights | ||
Weight, approx. | 49 g | |
last modified: | 02/01/2017 |