Technická data
Název:
SIPLUS ET 200SP F-DQ 4x24VDC/2A PM HF
Popis:
SIPLUS ET 200SP -25 ... +60 DEGREE WITH CONFORMAL COATING BASEDON 6ES7136-6DB00-0CA0 . ELECTRONIC MODULE, 4 F-DQ PROFISAFE, DC 24V/2A, 15 MM WIDTH, UP TO PL E (ISO 13849), UP TO SIL 3 (IEC 61508)
Technické informace:
General information | ||
Product type designation | F-DQ 4x24VDC HF | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated as of version | V12 | |
● STEP 7 configurable/integrated as of version | V5.5 SP3 / - | |
● PROFINET as of GSD version/GSD revision | V2.31 | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Input current | ||
Current consumption (rated value) | 75 mA; without load | |
Current consumption, max. | 21 mA; From the backplane bus | |
Output voltage | ||
Rated value (DC) | 24 V | |
Power | ||
Power available from the backplane bus | 70 mW | |
Power loss | ||
Power loss, typ. | 4 W | |
Address area | ||
Address space per module | ||
● Inputs | 5 byte | |
● Outputs | 5 byte | |
Digital outputs | ||
Number of digital outputs | 4 | |
Short-circuit protection | Yes | |
● Response threshold, typ. | > 3.3 A | |
Open-circuit detection | Yes | |
● Response threshold, typ. | 8 mA | |
Overload protection | Yes | |
● Response threshold, typ. | 2.9 A | |
Limitation of inductive shutdown voltage to | typ. 2*47V | |
Switching capacity of the outputs | ||
● with resistive load, max. | 2 A | |
● on lamp load, max. | 10 W | |
Load resistance range | ||
● lower limit | 12 Ω | |
● upper limit | 2 000 Ω | |
Output voltage | ||
● for signal "1", min. | 24 V; L+ (-0.5 V) | |
Output current | ||
● for signal "1" rated value | 2 A | |
● for signal "0" residual current, max. | 0.5 mA | |
Switching frequency | ||
● with resistive load, max. | 30 Hz; Symmetrical | |
● with inductive load, max. | 0.1 Hz; according to IEC 60947-5-1, DC-13, symmetrical | |
● on lamp load, max. | 10 Hz; Symmetrical | |
Total current of the outputs | ||
● Current per channel, max. | 2 A; Note derating data in the manual | |
● Current per module, max. | 6 A; Note derating data in the manual | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 500 m | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes, "Alarms/diagnostic messages" section in the manual | |
Substitute values connectable | No | |
Alarms | ||
● Diagnostic alarm | Yes | |
Diagnostics indication LED | ||
● RUN LED | Yes; Green LED | |
● ERROR LED | Yes; Red LED | |
● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | Yes; Red LED | |
● for module diagnostics | Yes; green/red DIAG LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | No | |
● between the channels and backplane bus | Yes | |
● between the channels and the power supply of the electronics | No | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -25 °C | |
● horizontal installation, max. | 60 °C | |
● vertical installation, min. | -25 °C | |
● vertical installation, max. | 50 °C | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 15 mm | |
Weights | ||
Weight, approx. | 57 g | |
last modified: | 02/01/2017 |