Technická data
Název:
SIPLUS ET 200SP CM PTP
Popis:
SIPLUS ET 200SP -40 ... +60 GRAD C STARTUP TEMP.: -25 DEGREE C WITH CONFORMAL COATING BASEDON 6ES7137-6AA00-0BA0 . CM PTP CM PTP COMMUNICATION MODUL FOR SERIAL CONNECTION RS422, RS485 AND RS232, FREEPORT, 3964(R), USS, MODBUS RTU MASTER, SLAVE, 115200 KBIT/S
Technické informace:
General information | ||
Product type designation | ET 200SP CM PtP | |
Firmware version | ||
● FW update possible | Yes | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated as of version | V12 / V12 | |
● STEP 7 configurable/integrated as of version | V5.5 SP2 with GSD file | |
● PROFIBUS as of GSD version/GSD revision | GSD as of Revision 5 | |
● PROFINET as of GSD version/GSD revision | GSDML V2.3 | |
Installation type/mounting | ||
Rack mounting possible | Yes | |
Rail mounting possible | Yes | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Input current | ||
Current consumption (rated value) | 29 mA | |
Power loss | ||
Power loss, typ. | 0.7 W | |
Address area | ||
Occupied address area | ||
● Inputs | 8 byte | |
1. Interface | ||
Interface types | ||
● RS 485 | Yes | |
● RS 422 | Yes | |
● RS 232 | Yes | |
Interface types | ||
RS 232 | ||
● Transmission rate, max. | 115.2 kbit/s | |
● Cable length, max. | 15 m | |
● RS 232 auxiliary signals | RTS, CTS, DTR, DSR, RI, DCD | |
RS 485 | ||
● Transmission rate, max. | 115.2 kbit/s | |
● Cable length, max. | 1 200 m | |
RS 422 | ||
● Transmission rate, max. | 115.2 kbit/s | |
● Cable length, max. | 1 200 m | |
● 4-wire full duplex connection | Yes | |
● 4-wire multipoint connection | Yes | |
Protocols | ||
Integrated protocols | ||
Freeport | ||
— Telegram length, max. | 2 kbyte | |
— Bits per character | 7 or 8 | |
— Number of stop bits | 1 or 2 bit | |
— Parity | None, even, odd, always 1, always 0, any | |
3964 (R) | ||
— Telegram length, max. | 2 kbyte | |
— Bits per character | 7 or 8 | |
— Number of stop bits | 1 or 2 bit | |
— Parity | None, even, odd, always 1, always 0, any | |
Modbus RTU master | ||
— Address area | 1 to 247, extended 1 to 65535 | |
— Number of slaves, max. | 32 | |
MODBUS RTU slave | ||
— Address area | 1 to 247, extended 1 to 65535 | |
Telegram buffer | ||
● Buffer memory for telegrams | 4 kbyte | |
● Number of telegrams which can be buffered | 255 | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
● Hardware interrupt | No | |
Diagnostic messages | ||
● Wire-break | Yes | |
Diagnostics indication LED | ||
● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | |
● for module diagnostics | Yes; green/red DIAG LED | |
● Receive RxD | Yes; Green LED | |
● Transmit TxD | Yes; Green LED | |
Potential separation | ||
between backplane bus and interface | Yes | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC (base isolation) | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin; Startup @ -25 °C | |
● horizontal installation, max. | 60 °C; = Tmax | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Decentralized operation | ||
to SIMATIC S7-300 | Yes | |
to SIMATIC S7-400 | Yes | |
to SIMATIC S7-1200 | Yes | |
to SIMATIC S7-1500 | Yes | |
to standard PROFINET controller | Yes | |
Dimensions | ||
Width | 15 mm | |
Height | 73 mm | |
Depth | 58 mm | |
Weights | ||
Weight, approx. | 30 g | |
last modified: | 02/03/2017 |