Technická data
Název:
SIPLUS ET 200SP TM TIMER DIDQ 10x24V
Popis:
SIPLUS ET 200SP TM TIMER DIDQ 10x24V -40 ... +60°C with conformal coating BasedOn: 6ES7138-6CG00-0BA0 . Time Based Digital Inputs and Outputs 4DI, 6DQ with timestamp COUNT, PWM, oversampling
Technické informace:
General information | ||
Product type designation | TM Timer DIDQ 10x24V | |
usable BaseUnits | BU type A0 | |
Product function | ||
● I&M data | Yes; I&M 0 | |
Supply voltage | ||
Load voltage L+ | ||
● Rated value (DC) | 24 V | |
● permissible range, lower limit (DC) | 19.2 V | |
● permissible range, upper limit (DC) | 28.8 V | |
● Reverse polarity protection | Yes; against destruction | |
Input current | ||
Current consumption, max. | 50 mA; without load | |
Encoder supply | ||
Number of outputs | 1 | |
24 V encoder supply | ||
● 24 V | Yes; L+ (-0.8 V) | |
● Short-circuit protection | Yes | |
● Output current, max. | 500 mA; Observe derating | |
Power loss | ||
Power loss, typ. | 1.5 W | |
Address area | ||
Occupied address area | ||
● Inputs | 26 byte | |
● Outputs | 32 byte | |
Digital inputs | ||
Number of digital inputs | 4 | |
Digital inputs, parameterizable | Yes | |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes | |
Digital input functions, parameterizable | ||
● Digital input with time stamp | Yes | |
— Number, max. | 4 | |
● Counter | Yes | |
— Number, max. | 3 | |
● Counter for incremental encoder | Yes | |
— Number, max. | 1 | |
● Digital input with oversampling | Yes | |
— Number, max. | 4 | |
● HW enable for digital input | Yes | |
— Number, max. | 1 | |
● HW enable for digital output | Yes | |
— Number, max. | 3 | |
Input voltage | ||
● Type of input voltage | DC | |
● Rated value (DC) | 24 V | |
● for signal "0" | -30 to +5V | |
● for signal "1" | +11 to +30V | |
● permissible voltage at input, min. | -30 V | |
● permissible voltage at input, max. | 30 V | |
Input current | ||
● for signal "1", typ. | 2.5 mA | |
Input delay (for rated value of input voltage) | ||
● Minimum pulse width for program reactions | 3 µs for parameterization "none" | |
for standard inputs | ||
— parameterizable | Yes; none / 0.05 / 0.1 / 0.4 / 0.8 ms | |
— at "0" to "1", min. | 4 µs | |
— at "1" to "0", min. | 4 µs | |
Cable length | ||
● shielded, max. | 1 000 m; Depending on sensor, cable quality and rate of change | |
● unshielded, max. | 600 m; Depending on sensor, cable quality and rate of change | |
Digital outputs | ||
Type of digital output | Transistor | |
Number of digital outputs | 6 | |
Current-sinking | Yes; With High Speed output | |
Current-sourcing | Yes | |
Digital outputs, parameterizable | Yes | |
Short-circuit protection | Yes; electronic/thermal | |
● Response threshold, typ. | 1.7 A with Standard output, 0.5 A with High Speed output | |
Limitation of inductive shutdown voltage to | -0.8 V | |
Digital output functions, parameterizable | ||
● Digital output with time stamp | Yes | |
— Number, max. | 6 | |
● PWM output | Yes | |
— Number, max. | 6 | |
● Digital output with oversampling | Yes | |
— Number, max. | 6 | |
Switching capacity of the outputs | ||
● with resistive load, max. | 0.5 A; 0.1 A with High Speed output | |
● on lamp load, max. | 5 W; 1 W with High Speed output | |
Load resistance range | ||
● lower limit | 48 Ω; 240 ohm with High Speed output | |
● upper limit | 12 kΩ | |
Output voltage | ||
● Type of output voltage | DC | |
● for signal "0", max. | 1 V; With High Speed output | |
● for signal "1", min. | 23.2 V; L+ (-0.8 V) | |
Output current | ||
● for signal "1" rated value | 0.5 A; 0.1 A with High Speed output, observe derating | |
● for signal "1" permissible range, max. | 0.6 A; 0.12 A with High Speed output, observe derating | |
● for signal "1" minimum load current | 2 mA | |
● for signal "0" residual current, max. | 0.5 mA | |
Output delay with resistive load | ||
● "0" to "1", max. | 1 µs; With High Speed output, 5 µs with Standard output | |
● "1" to "0", max. | 1 µs; With High Speed output, 6 µs with Standard output | |
Switching frequency | ||
● with resistive load, max. | 10 kHz | |
● on lamp load, max. | 10 Hz | |
Total current of the outputs | ||
● Current per module, max. | 3.5 A; Observe derating | |
Cable length | ||
● shielded, max. | 1 000 m; Depending on load and cable quality | |
● unshielded, max. | 600 m; Depending on load and cable quality | |
Encoder | ||
Connectable encoders | ||
● Incremental encoder (asymmetrical) | Yes | |
● 24 V initiator | Yes | |
● 2-wire sensor | Yes | |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA | |
Encoder signals, incremental encoder (asymmetrical) | ||
● Input voltage | 24 V | |
● Input frequency, max. | 50 kHz | |
● Counting frequency, max. | 200 kHz; with quadruple evaluation | |
● Cable length, shielded, max. | 600 m; Depending on input frequency, encoder and cable quality; max. 200 m at 50 kHz | |
● Incremental encoder with A/B tracks, 90° phase offset | Yes | |
● Pulse encoder | Yes | |
Encoder signal 24 V | ||
— permissible voltage at input, min. | -30 V | |
— permissible voltage at input, max. | 30 V | |
Interface types | ||
● Input characteristic curve in accordance with IEC 61131, type 3 | Yes | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | Yes | |
Bus cycle time (TDP), min. | 375 µs | |
Jitter, max. | 1 µs | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Substitute values connectable | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
Diagnostic messages | ||
● Monitoring the supply voltage | Yes | |
● Short-circuit | Yes | |
Diagnostics indication LED | ||
● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | |
● Channel status display | Yes | |
● for module diagnostics | Yes; green/red DIAG LED | |
Integrated Functions | ||
Number of counters | 3 | |
Counting frequency (counter) max. | 200 kHz; with quadruple evaluation | |
Counting functions | ||
● Continuous counting | Yes | |
Potential separation | ||
Potential separation channels | ||
● between the channels and backplane bus | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C | |
● horizontal installation, max. | 60 °C; = Tmax; see Derating BasedOn (e.g. manual) | |
● vertical installation, min. | 0 °C | |
● vertical installation, max. | 50 °C; = Tmax; see Derating BasedOn (e.g. manual) | |
Relative humidity | ||
● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Decentralized operation | ||
to SIMATIC S7-1500 | Yes | |
Dimensions | ||
Width | 15 mm | |
Height | 73 mm | |
Depth | 58 mm | |
Weights | ||
Weight, approx. | 45 g | |
last modified: | 09/25/2017 |