Technická data
Název:
SIPLUS ET 200SP IM155-6DP HF
Popis:
SIPLUS ET 200SP -40 ... +70 GRAD C Startup -25°C fehlt WITH CONFORMAL COATING BASEDON 6ES7155-6BA00-0CN0 . PROFIBUS INTERFACEMODUL, IM155-6DP HIGH FEATURE, MAX. 32 PERIPHERIEMODULE, MULTI HOT SWAP, INCL. SERVERMODUL, INCL. PROFIBUS STECKER
Technické informace:
General information | ||
Product type designation | IM155-6DP HF with PROFIBUS connector and server module | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
Engineering with | ||
● STEP 7 configurable/integrated as of version | V5.5 SP3 / - | |
● PROFIBUS as of GSD version/GSD revision | GSD as of Revision 5 | |
Supply voltage | ||
Type of supply voltage | DC | |
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Mains buffering | ||
● Mains/voltage failure stored energy time | 5 ms | |
Input current | ||
Current consumption, max. | 250 mA | |
Inrush current, max. | 4.5 A | |
Power loss | ||
Power loss, typ. | 1.5 W | |
Address area | ||
Address space per station | ||
● Address space per station, max. | 244 byte | |
Interfaces | ||
Number of PROFIBUS interfaces | 1 | |
1. Interface | ||
Interface types | ||
● RS 485 | Yes | |
● Output current of the interface, max. | 90 mA | |
Functionality | ||
● PROFIBUS DP slave | Yes | |
Interface types | ||
RS 485 | ||
● Transmission rate, max. | 12 Mbit/s | |
Protocols | ||
PROFIBUS | ||
Services | ||
— SYNC capability | Yes | |
— FREEZE capability | Yes | |
— DPV0 | No | |
— DPV1 | Yes | |
Interrupts/diagnostics/status information | ||
Status indicator | Yes | |
Alarms | Yes | |
Diagnostic functions | Yes | |
Diagnostics indication LED | ||
● RUN LED | Yes; Green LED | |
● ERROR LED | Yes; Red LED | |
● MAINT LED | Yes; yellow LED | |
● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | |
● Connection display DP | Yes; Green DP LED | |
Potential separation | ||
between PROFIBUS DP and all other circuit components | Yes | |
between supply and all other circuits | Yes | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC (base isolation) | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin; Startup @ -25 °C | |
● horizontal installation, max. | 70 °C; = Tmax | |
● vertical installation, min. | -40 °C; = Tmin; Startup @ -25 °C | |
● vertical installation, max. | 50 °C; = Tmax | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 50 mm | |
Height | 117 mm | |
Depth | 74 mm | |
Weights | ||
Weight, approx. | 150 g | |
last modified: | 02/03/2017 |