Technická data
Název:
SIPLUS ET 200SP CPU 1515SP PC 4GB
Popis:
SIPLUS ET 200SP CPU 1515SP PC 4 0 ... +60 °C with conformal coating BasedOn:6ES7677-2AA31-0EB0 . CPU 1515SP PC. 4 GB RAM, 8 GB CFAST mit WES 7 E 32 Bit preinstalled, with S7-1500 Software Controlle CPU 1505SP V2.0 preinstalled, Interfaces: 1x Slot CFAST, 1x Slot SD/MMC, 1x Pluf for ET 200SP Bus- Adaption PROFINET, 1x 10/100/1000 MBit/s Ethernet, 3x USB,1x DVI-I,Restore-DVD Documentation on DVD,
Technické informace:
General information | ||
Product type designation | CPU 1515SP PC | |
HW functional status | FS05 | |
Firmware version | V2.0 | |
Installed software | ||
● Visualization | No | |
● Control | S7-1500 Software Controller CPU 1505SP V2.0 | |
Configuration control | ||
via dataset | Yes | |
Control elements | ||
Mode selector switch | 1 | |
Supply voltage | ||
Type of supply voltage | 24 V DC | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Mains buffering | ||
● Mains/voltage failure stored energy time | 5 ms | |
Input current | ||
Current consumption (rated value) | 1.5 A; Full processor load, incl. ET 200SP modules and using USB | |
Current consumption (in no-load operation), typ. | 0.6 A | |
Inrush current, max. | 4.7 A; Rated value | |
Power | ||
Active power input, max. | 36 W; incl. ET 200SP modules and using USB | |
Infeed power to the backplane bus | 8.75 W | |
Power loss | ||
Power loss, typ. | 15 W; without ET 200SP modules and without using USB | |
Processor | ||
Processor | Dual-Core 1 GHz, AMD G Series APU T40E | |
Memory | ||
Type of memory | DDR3-SDRAM | |
Main memory | 4 GB RAM | |
Flash Disk | 8 GB | |
CFast memory card | Yes; 8 GB flash memory | |
SIMATIC memory card required | No | |
Work memory | ||
● integrated (for program) | 1 Mbyte | |
● integrated (for data) | 5 Mbyte | |
● integrated (for CPU function library of CPU Runtime) | 10 Mbyte | |
Load memory | ||
● integrated (on PC mass storage) | 320 Mbyte | |
Backup | ||
● with UPS | Yes; all memory areas declared retentive | |
● with non-volatile memory | Yes | |
CPU processing times | ||
for bit operations, typ. | 10 ns | |
for word operations, typ. | 12 ns | |
for fixed point arithmetic, typ. | 16 ns | |
for floating point arithmetic, typ. | 64 ns | |
CPU-blocks | ||
Number of elements (total) | 6 000; In addition to blocks such as DBs, FBs and FCs, UDTs, global constants, etc. are also regarded as elements | |
DB | ||
● Number, max. | 5 999; Number range: 1 to 65535 | |
● Size, max. | 5 Mbyte | |
FB | ||
● Number, max. | 5 998; Number range: 1 to 65535 | |
● Size, max. | 512 kbyte | |
FC | ||
● Number, max. | 5 999; Number range: 1 to 65535 | |
● Size, max. | 512 kbyte | |
OB | ||
● Size, max. | 1 048 kbyte | |
● Number of free cycle OBs | 100 | |
● Number of time alarm OBs | 20 | |
● Number of delay alarm OBs | 20 | |
● Number of cyclic interrupt OBs | 20 | |
● Number of process alarm OBs | 50 | |
● Number of DPV1 alarm OBs | 3 | |
● Number of isochronous mode OBs | 1 | |
● Number of technology synchronous alarm OBs | 2 | |
● Number of startup OBs | 100 | |
● Number of asynchronous error OBs | 4 | |
● Number of synchronous error OBs | 2 | |
● Number of diagnostic alarm OBs | 1 | |
Nesting depth | ||
● per priority class | 24 | |
Counters, timers and their retentivity | ||
S7 counter | ||
● Number | 2 048 | |
Retentivity | ||
— adjustable | Yes | |
IEC counter | ||
● Number | Any (only limited by the main memory) | |
Retentivity | ||
— adjustable | Yes | |
S7 times | ||
● Number | 2 048 | |
Retentivity | ||
— adjustable | Yes | |
IEC timer | ||
● Number | Any (only limited by the main memory) | |
Retentivity | ||
— adjustable | Yes | |
Data areas and their retentivity | ||
Retentive data area (incl. timers, counters, flags), max. | 410 kbyte; For storage in NVRAM; for storage in mass storage 5 242 020 bytes | |
Flag | ||
● Number, max. | 16 kbyte | |
● Number of clock memories | 8; 8 clock memory bits, grouped into one clock memory byte | |
Data blocks | ||
● Retentivity adjustable | Yes | |
● Retentivity preset | No | |
Local data | ||
● per priority class, max. | 64 kbyte; max. 16 KB per block | |
Address area | ||
Number of IO modules | 8 192 | |
I/O address area | ||
● Inputs | 32 kbyte; All inputs are in the process image | |
● Outputs | 32 kbyte; All outputs are in the process image | |
of which per assigned PC interface | ||
— Inputs (volume) | 8 kbyte | |
— Outputs (volume) | 8 kbyte | |
Subprocess images | ||
● Number of subprocess images, max. | 32 | |
Hardware configuration | ||
Integrated power supply | Yes | |
Number of distributed IO systems | 20 | |
Number of DP masters | ||
● Via CM | 1 | |
Rack | ||
● Modules per rack, max. | 64; CPU 1515SP PC + 64 modules + server module | |
● Number of lines, max. | 1 | |
PtP CM | ||
● Number of PtP CMs | the number of connectable PtP CMs is only limited by the number of available slots | |
Time of day | ||
Clock | ||
● Type | Hardware clock | |
● Hardware clock (real-time) | Yes; Resolution: 1 s | |
● Backup time | 6 wk; At 40 °C ambient temperature, typically | |
● Deviation per day, max. | 10 s; Typ.: 2 s | |
Clock synchronization | ||
● supported | Yes | |
● to DP, master | No | |
● on Ethernet via NTP | Yes | |
● on Windows clock, slave | Yes | |
Interfaces | ||
Number of industrial Ethernet interfaces | 2 | |
Number of PROFINET interfaces | 1 | |
Number of PROFIBUS interfaces | 1 | |
Number of RS 485 interfaces | 1; Via CM DP module | |
Number of USB interfaces | 3; 3x USB 2.0 on the front, 500 mA each – of which 2x 500 mA and 1x 100 mA simultaneously | |
Number of SD card slots | 1 | |
Video interfaces | ||
● Graphics interface | 1x DVI-I | |
1. Interface | ||
Interface type | PROFINET | |
automatic detection of transmission rate | Yes | |
Autonegotiation | Yes | |
Autocrossing | Yes | |
Interface types | ||
● Number of ports | 2 | |
● integrated switch | Yes | |
● RJ 45 (Ethernet) | Yes; Via BusAdapter BA 2x RJ45 | |
— Transmission rate, max. | 100 Mbit/s | |
— Industrial Ethernet status LED | Yes | |
● BusAdapter (PROFINET) | Yes; Applicable BusAdapter: BA 2x RJ45, BA 2x FC | |
Functionality | ||
● Number of connections via this interface | 88 | |
● PROFINET IO Controller | Yes | |
● PROFINET IO Device | Yes | |
● SIMATIC communication | Yes | |
● Open IE communication | Yes | |
● Web server | Yes | |
PROFINET IO Controller | ||
Services | ||
— Isochronous mode | Yes | |
— shortest clock pulse | 500 µs | |
— IRT | Yes | |
— MRP | Yes | |
— MRPD | Yes | |
— Prioritized startup | Yes; Max. 32 PROFINET devices | |
— Number of connectable IO Devices, max. | 128 | |
— Of which IO devices with IRT, max. | 64 | |
— of which in line, max. | 64 | |
— Number of connectable IO Devices for RT, max. | 128 | |
— of which in line, max. | 128 | |
— Number of IO Devices that can be simultaneously activated/deactivated, max. | 8 | |
— IO Devices changing during operation (partner ports), supported | Yes | |
— Number of IO Devices per tool, max. | 8 | |
— Updating times | The minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data | |
Update time for IRT | ||
— for send cycle of 500 µs | 500 µs to 8 ms | |
— for send cycle of 1 ms | 1 ms to 16 ms | |
— for send cycle of 2 ms | 2 ms to 32 ms | |
— for send cycle of 4 ms | 4 ms to 64 ms | |
— With IRT and parameterization of "odd" send cycles | Update time = set "odd" send clock (any multiple of 125 µs: 375 µs, 625 µs ... 3 875 µs) | |
Update time for RT | ||
— for send cycle of 500 µs | 500 µs to 256 ms | |
— for send cycle of 1 ms | 1 ms to 512 ms | |
— for send cycle of 2 ms | 2 ms to 512 ms | |
— for send cycle of 4 ms | 4 ms to 512 ms | |
PROFINET IO Device | ||
Services | ||
— Isochronous mode | No | |
— IRT | Yes | |
— MRP | Yes | |
— MRPD | Yes | |
— Prioritized startup | Yes | |
— Shared device | Yes | |
— Number of IO Controllers with shared device, max. | 4 | |
2. Interface | ||
Interface type | Integrated Ethernet interface | |
automatic detection of transmission rate | Yes | |
Autonegotiation | Yes | |
Autocrossing | Yes | |
Interface types | ||
● Number of ports | 1 | |
● RJ 45 (Ethernet) | Yes; Integrated | |
— Transmission rate, max. | 1 000 Mbit/s | |
— Industrial Ethernet status LED | No | |
3. Interface | ||
Interface type | PROFIBUS with CM DP | |
Interface types | ||
● RS 485 | Yes | |
Functionality | ||
● Number of connections via this interface | 44 | |
● PROFIBUS DP master | Yes | |
● PROFIBUS DP slave | Yes | |
● SIMATIC communication | Yes | |
DP master | ||
Services | ||
— Equidistance | No | |
— Isochronous mode | No | |
— Number of connectable DP slaves, max. | 125 | |
DP slave | ||
Services | ||
— Equidistance | No | |
— Isochronous mode | No | |
Interface types | ||
RS 485 | ||
● Transmission rate, max. | 12 Mbit/s | |
Protocols | ||
Number of connections | ||
● Number of connections, max. | 88 | |
● Number of connections reserved for ES/HMI/web | 10 | |
● Number of S7 routing paths | 16 | |
SIMATIC communication | ||
● PG/OP communication | Yes | |
● S7 routing | Yes | |
● S7 communication, as server | Yes | |
● S7 communication, as client | Yes | |
● User data per job, max. | 64 kbyte | |
Open IE communication | ||
● TCP/IP | Yes | |
— Data length, max. | 64 kbyte | |
● ISO-on-TCP (RFC1006) | Yes | |
— Data length, max. | 64 kbyte | |
● UDP | Yes | |
— Data length, max. | 1 472 kbyte | |
● SNMP | Yes | |
● DCP | Yes | |
● LLDP | Yes | |
Web server | ||
● HTTP | Yes; Via Windows and PROFINET interface | |
● HTTPS | Yes; Only via PROFINET interface | |
OPC UA | ||
● OPC UA Server | Data access (read, write, subscribe), runtime license required | |
— Application authentication | Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 | |
— Security policies | Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 | |
— User authentication | "anonymous" or by user name & password | |
Further protocols | ||
● MODBUS | Yes; MODBUS TCP | |
Media redundancy | ||
● Switchover time on line break, typ. | 200 ms | |
● Number of stations in the ring, max. | 50 | |
S7 message functions | ||
Number of login stations for message functions, max. | 32 | |
Program alarms | Yes | |
Number of configurable program alarms | 10 000 | |
Number of simultaneously active program alarms | ||
● Number of program alarms | 1 000 | |
● Number of alarms for system diagnostics | 200 | |
● Number of alarms for motion technology objects | 160 | |
Test commissioning functions | ||
Joint commission (Team Engineering) | Yes; Parallel online access possible for up to 8 engineering systems | |
Status block | Yes; up to 8 simultaneously | |
Single step | No | |
Status/control | ||
● Status/control variable | Yes | |
● Variables | Inputs, outputs, memory bits, DB, times, counters | |
● Number of variables, max. | ||
— of which status variables, max. | 200 | |
— of which control variables, max. | 200 | |
Forcing | ||
● Forcing | Yes | |
● Forcing, variables | Inputs, outputs | |
● Number of variables, max. | 200 | |
Diagnostic buffer | ||
● present | Yes | |
● Number of entries, max. | 1 000 | |
— of which powerfail-proof | 300 | |
Traces | ||
● Number of configurable Traces | 4 | |
● Memory size per trace, max. | 512 kbyte | |
Interrupts/diagnostics/status information | ||
Diagnostics indication LED | ||
● RUN/STOP LED | Yes | |
● ERROR LED | Yes | |
● MAINT LED | Yes | |
Supported technology objects | ||
Motion Control | Yes | |
● Number of available Motion Control resources for technology objects (except cam disks) | 2 400 | |
● Required Motion Control resources | ||
— per speed-controlled axis | 40; per axis | |
— per positioning axis | 80; per axis | |
— per synchronous axis | 160; per axis | |
— per external encoder | 80; per external encoder | |
— per output cam | 20; per cam | |
— per cam track | 160; per cam track | |
— per probe | 40; per probe | |
● Positioning axis | ||
— Number of positioning axes at motion control cycle of 4 ms (typical value) | 5 | |
— Number of positioning axes at motion control cycle of 8 ms (typical value) | 12 | |
Controller | ||
● PID_Compact | Yes; Universal PID controller with integrated optimization | |
● PID_3Step | Yes; PID controller with integrated optimization for valves | |
● PID-Temp | Yes; PID controller with integrated optimization for temperature | |
Counting and measuring | ||
● High-speed counter | Yes | |
EMC | ||
Emission of radio interference acc. to EN 55 011 | ||
● Limit class A, for use in industrial areas | Yes | |
Standards, approvals, certificates | ||
CE mark | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | 0 °C | |
● max. | 60 °C; Up to 60 °C with max. 32 ET 200SP modules and 3x 100 mA USB load; up to 55 °C with max. 64 ET 200SP modules and 2x max. 500 mA and 1x max. 100 mA USB load | |
● horizontal installation, min. | 0 °C; = Tmin | |
● horizontal installation, max. | 60 °C; = Tmax; up to 60 °C with max. 32 ET 200SP modules and 3x 100 mA USB load; up to 55 °C with max. 64 ET 200SP modules and 2x max. 500 mA and 1x max. 100 mA USB load | |
● vertical installation, min. | 0 °C; = Tmin | |
● vertical installation, max. | 50 °C; = Tmax; at max. 32 ET 200SP modules and 3x 100 mA USB load | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Relative humidity | ||
● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Vibrations | ||
● Operation, tested according to IEC 60068-2-6 | Yes | |
● Transport, tested acc. to IEC 60068-2-6 | Yes | |
Shock test | ||
● tested according to IEC 60068-2-27 | Yes | |
● tested according to IEC 60068-2-6 | Yes | |
Shock testing | ||
● tested according to IEC 60068-2-29 | Yes | |
● Storage/transport, tested acc. to IEC 60068-2-27 | Yes | |
Operating systems | ||
Operating systems | Windows Embedded Standard 7 E 32-bit | |
Configuration | ||
Programming | ||
Programming language | ||
— LAD | Yes | |
— FBD | Yes | |
— STL | Yes | |
— SCL | Yes | |
— CFC | No | |
— GRAPH | Yes | |
Know-how protection | ||
● User program protection/password protection | Yes | |
● Copy protection | Yes | |
● Block protection | Yes | |
Access protection | ||
● Protection level: Write protection | Yes | |
● Protection level: Read/write protection | Yes | |
● Protection level: Complete protection | Yes | |
Cycle time monitoring | ||
● lower limit | adjustable minimum cycle time | |
● upper limit | adjustable maximum cycle time | |
Open Development interfaces | ||
● Size of ODK SO file, max. | 3.8 Mbyte | |
Peripherals/Options | ||
Peripherals | ||
● SD card | Optionally for additional mass storage | |
Dimensions | ||
Width | 160 mm | |
Height | 117 mm | |
Depth | 75 mm | |
Weights | ||
Weight, approx. | 0.83 kg | |
last modified: | 09/25/2017 |