Technická data
Název:
SIPLUS ET 200SP AI 4xRTD/TC HF
Popis:
SIPLUS ET 200SP, ANALOG INPUT MODULE, AI 4XRTD/TC HIGH FEATURE, -40 ... +60 DEGREES C Startup -25°C WITH CONFORMAL COATING BASED ON 6ES7134-6JD00-0CA1 . FITS TO BU-TYPE A0, A1, COLOR CODE CC00, CHANNEL DIAGNOSIS, 16BIT, +/-0,1%, 2-/3-/4-WIRE
Technické informace:
General information | ||
Product type designation | AI 4xRTD/TC 2-/3-/4-wire HF | |
Product function | ||
● I&M data | Yes | |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated as of version | V11 SP2 with HSP0024 / - | |
● STEP 7 configurable/integrated as of version | V5.5 SP2 with GSD file / - | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Input current | ||
Current consumption, max. | 35 mA | |
Power loss | ||
Power loss, typ. | 0.75 W | |
Address area | ||
Address space per module | ||
● Address space per module, max. | 8 byte | |
Analog inputs | ||
Number of analog inputs | 4 | |
permissible input voltage for voltage input (destruction limit), max. | 30 V | |
Constant measurement current for resistance-type transmitter, typ. | 2 mA | |
Cycle time (all channels), min. | Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels); for line compensation in case of a three-wire connection, an additional cycle is necessary | |
Technical unit for temperature measurement adjustable | Yes; °C/°F/K | |
Input ranges (rated values), voltages | ||
● -1 V to +1 V | Yes; 16 bit incl. sign | |
● Input resistance (-1 V to +1 V) | 10 MΩ | |
● -250 mV to +250 mV | Yes; 16 bit incl. sign | |
● Input resistance (-250 mV to +250 mV) | 10 MΩ | |
● -50 mV to +50 mV | Yes; 16 bit incl. sign | |
● Input resistance (-50 mV to +50 mV) | 10 MΩ | |
● -80 mV to +80 mV | Yes; 16 bit incl. sign | |
● Input resistance (-80 mV to +80 mV) | 10 MΩ | |
Input ranges (rated values), thermocouples | ||
● Type B | Yes; 16 bit incl. sign | |
● Input resistance (Type B) | 1 MΩ | |
● Type C | Yes; 16 bit incl. sign | |
● Input resistance (Type C) | 1 MΩ | |
● Type E | Yes; 16 bit incl. sign | |
● Input resistance (Type E) | 1 MΩ | |
● Type J | Yes; 16 bit incl. sign | |
● Input resistance (type J) | 1 MΩ | |
● Type K | Yes; 16 bit incl. sign | |
● Input resistance (Type K) | 1 MΩ | |
● Type L | Yes; 16 bit incl. sign | |
● Input resistance (Type L) | 1 MΩ | |
● Type N | Yes; 16 bit incl. sign | |
● Input resistance (Type N) | 1 MΩ | |
● Type R | Yes; 16 bit incl. sign | |
● Input resistance (Type R) | 1 MΩ | |
● Type S | Yes; 16 bit incl. sign | |
● Input resistance (Type S) | 1 MΩ | |
● Type T | Yes; 16 bit incl. sign | |
● Input resistance (Type T) | 1 MΩ | |
● Type U | Yes; 16 bit incl. sign | |
● Input resistance (Type U) | 1 MΩ | |
● Type TXK/TXK(L) to GOST | Yes; 16 bit incl. sign | |
● Input resistance (Type TXK/TXK(L) to GOST) | 1 MΩ | |
Input ranges (rated values), resistance thermometer | ||
● Cu 10 | Yes; 16 bit incl. sign | |
● Input resistance (Cu 10) | 1 MΩ | |
● Ni 100 | Yes; 16 bit incl. sign | |
● Input resistance (Ni 100) | 1 MΩ | |
● Ni 1000 | Yes; 16 bit incl. sign | |
● Input resistance (Ni 1000) | 1 MΩ | |
● LG-Ni 1000 | Yes; 16 bit incl. sign | |
● Input resistance (LG-Ni 1000) | 1 MΩ | |
● Ni 120 | Yes; 16 bit incl. sign | |
● Input resistance (Ni 120) | 1 MΩ | |
● Ni 200 | Yes; 16 bit incl. sign | |
● Input resistance (Ni 200) | 1 MΩ | |
● Ni 500 | Yes; 16 bit incl. sign | |
● Input resistance (Ni 500) | 1 MΩ | |
● Pt 100 | Yes; 16 bit incl. sign | |
● Input resistance (Pt 100) | 1 MΩ | |
● Pt 1000 | Yes; 16 bit incl. sign | |
● Input resistance (Pt 1000) | 1 MΩ | |
● Pt 200 | Yes; 16 bit incl. sign | |
● Input resistance (Pt 200) | 1 MΩ | |
● Pt 500 | Yes; 16 bit incl. sign | |
● Input resistance (Pt 500) | 1 MΩ | |
Input ranges (rated values), resistors | ||
● 0 to 150 ohms | Yes; 15 bit | |
● Input resistance (0 to 150 ohms) | 1 MΩ | |
● 0 to 300 ohms | Yes; 15 bit | |
● Input resistance (0 to 300 ohms) | 1 MΩ | |
● 0 to 600 ohms | Yes; 15 bit | |
● Input resistance (0 to 600 ohms) | 1 MΩ | |
● 0 to 3000 ohms | Yes; 15 bit | |
● Input resistance (0 to 3000 ohms) | 1 MΩ | |
● 0 to 6000 ohms | Yes; 15 bit | |
● Input resistance (0 to 6000 ohms) | 1 MΩ | |
● PTC | Yes; 15 bit | |
● Input resistance (PTC) | 1 MΩ | |
Thermocouple (TC) | ||
Temperature compensation | ||
— parameterizable | Yes | |
— Reference channel of the module | Yes | |
— internal comparison point | Yes | |
— Reference channel of the group | Yes | |
— fixed reference temperature | Yes | |
Cable length | ||
● shielded, max. | 200 m; 50 m with thermocouples | |
Analog value generation for the inputs | ||
Measurement principle | integrating (Sigma-Delta) | |
Integration and conversion time/resolution per channel | ||
● Resolution with overrange (bit including sign), max. | 16 bit | |
● Integration time, parameterizable | Yes | |
● Basic conversion time, including integration time (ms) | ||
— additional processing time for wire-break check | 2 ms; In the ranges resistance thermometers, resistors and thermocouples | |
— additional power line wire-break check | 2 ms; for 3/4 wire transducer (resistance thermometer and resistor) | |
● Interference voltage suppression for interference frequency f1 in Hz | 16.6 / 50 / 60 Hz | |
● Conversion time (per channel) | 180 / 60 / 50 ms | |
Smoothing of measured values | ||
● parameterizable | Yes | |
● Step: None | Yes | |
● Step: low | Yes | |
● Step: Medium | Yes | |
● Step: High | Yes | |
Encoder | ||
Connection of signal encoders | ||
● for voltage measurement | Yes | |
● for resistance measurement with two-wire connection | Yes | |
● for resistance measurement with three-wire connection | Yes | |
● for resistance measurement with four-wire connection | Yes | |
Errors/accuracies | ||
Linearity error (relative to input range), (+/-) | 0.01 %; +/- 0.1 % for resistance thermometers and resistance | |
Temperature error (relative to input range), (+/-) | 0.0009 %/K; +/- 0.005 %/K at thermocouple | |
Crosstalk between the inputs, min. | -50 dB | |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % | |
Operational error limit in overall temperature range | ||
● Voltage, relative to input range, (+/-) | 0.1 % | |
● Resistance, relative to input range, (+/-) | 0.1 % | |
Basic error limit (operational limit at 25 °C) | ||
● Voltage, relative to input range, (+/-) | 0.05 % | |
● Resistance, relative to input range, (+/-) | 0.05 % | |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | ||
● Series mode interference (peak value of interference < rated value of input range), min. | 70 dB | |
● Common mode voltage, max. | 10 V | |
● Common mode interference, min. | 90 dB | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
● Limit value alarm | Yes; two upper and two lower limit values in each case | |
Diagnostic messages | ||
● Monitoring the supply voltage | Yes | |
● Wire-break | Yes | |
● Overflow/underflow | Yes | |
Diagnostics indication LED | ||
● Monitoring of the supply voltage (PWR-LED) | Yes; Green LED | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | Yes; Red LED | |
● for module diagnostics | Yes; Green/red LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | No | |
● between the channels and backplane bus | Yes | |
● between the channels and the power supply of the electronics | Yes | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC | |
between the inputs (UCM) | 10 V DC | |
Isolation | ||
Isolation tested with | 707 V DC | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin; Startup @ -25 °C | |
● horizontal installation, max. | 60 °C; = Tmax | |
● vertical installation, min. | -40 °C; = Tmin; Startup @ -25 °C | |
● vertical installation, max. | 50 °C; = Tmax | |
Extended ambient conditions | ||
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 15 mm | |
Height | 73 mm | |
Depth | 58 mm | |
Weights | ||
Weight, approx. | 30 g | |
last modified: | 02/03/2017 |