Technická data
Název:
SIPLUS ET 200SP AQ 4xU/I ST
Popis:
SIPLUS ET 200SP, ANALOG OUTPUT MODULE, AQ 4XU/I STANDARD, -40 ... +70 DEGREES C Startup -25°C WITH CONFORMAL COATING BASED ON 6ES7135-6HD00-0BA1 . FITS TO BU-TYPE A0, A1, COLOR CODE CC00, MODULE DIAGNOSIS, 16BIT, +/-0,3%
Technické informace:
General information | ||
Product type designation | AQ 4xU/I ST | |
Product function | ||
● I&M data | Yes | |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated as of version | V11 SP2 with HSP0024 / - | |
● STEP 7 configurable/integrated as of version | V5.5 SP2 with GSD file / - | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Input current | ||
Current consumption, max. | 150 mA | |
Power loss | ||
Power loss, typ. | 1.5 W | |
Analog outputs | ||
Number of analog outputs | 4; > +60 °C max. 2x +/- 10 V permissible | |
Voltage output, short-circuit current, max. | 45 mA | |
Cycle time (all channels), min. | 5 ms | |
Output ranges, voltage | ||
● 0 to 10 V | Yes; 15 bit | |
● 1 V to 5 V | Yes; 13 bit | |
● -5 V to +5 V | Yes; 15 bit incl. sign | |
● -10 V to +10 V | Yes; 16 bit incl. sign | |
Output ranges, current | ||
● 0 to 20 mA | Yes; 15 bit | |
● -20 mA to +20 mA | Yes; 16 bit incl. sign | |
● 4 mA to 20 mA | Yes; 14 bit | |
Connection of actuators | ||
● for voltage output two-wire connection | Yes | |
● for voltage output four-wire connection | Yes | |
● for current output two-wire connection | Yes | |
Load impedance (in rated range of output) | ||
● with voltage outputs, min. | 2 kΩ | |
● with voltage outputs, capacitive load, max. | 1 µF | |
● with current outputs, max. | 500 Ω | |
● with current outputs, inductive load, max. | 1 mH | |
Destruction limits against externally applied voltages and currents | ||
● Voltages at the outputs | 30 V | |
Cable length | ||
● shielded, max. | 200 m | |
Analog value generation for the outputs | ||
Settling time | ||
● for resistive load | 0.1 ms | |
● for capacitive load | 1 ms | |
● for inductive load | 0.5 ms | |
Errors/accuracies | ||
Linearity error (relative to output range), (+/-) | 0.03 % | |
Temperature error (relative to output range), (+/-) | 0.005 %/K | |
Crosstalk between the outputs, min. | -50 dB | |
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.05 % | |
Operational error limit in overall temperature range | ||
● Voltage, relative to output range, (+/-) | 0.5 % | |
● Current, relative to output range, (+/-) | 0.5 % | |
Basic error limit (operational limit at 25 °C) | ||
● Voltage, relative to output range, (+/-) | 0.3 % | |
● Current, relative to output range, (+/-) | 0.3 % | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Substitute values connectable | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
Diagnostic messages | ||
● Monitoring the supply voltage | Yes | |
● Wire-break | Yes | |
● Short-circuit | Yes | |
● Overflow/underflow | Yes | |
Diagnostics indication LED | ||
● Monitoring of the supply voltage (PWR-LED) | Yes; Green LED | |
● Channel status display | Yes; Green LED | |
● for module diagnostics | Yes; Green/red LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | No | |
● between the channels and backplane bus | Yes | |
● between the channels and the power supply of the electronics | Yes | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC | |
Isolation | ||
Isolation tested with | 707 V DC | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin; Startup @ -25 °C | |
● horizontal installation, max. | 70 °C; = Tmax; > +60 °C max. 2x +/- 10 V permissible | |
● vertical installation, min. | -40 °C; = Tmin; Startup @ -25 °C | |
● vertical installation, max. | 50 °C; = Tmax | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 15 mm | |
Weights | ||
Weight, approx. | 31 g | |
last modified: | 02/03/2017 |