Technická data
Název:
SIPLUS ET200SP DQ 4x24VDC/2A ST
Popis:
SIPLUS ET 200SP, DIGITAL OUTPUT MODULE, DQ 4X24VDC/2A STANDARD, -40 ... +70 DEGREES C Startup -25°C WITH CONFORMAL COATING BASED ON 6ES7132-6BD20-0BA0 . FITS TO BU-TYPE A0, COLOR CODE CC02, MODULE DIAGNOSIS
Technické informace:
General information | ||
Product type designation | DQ 4x24VDC/2A ST | |
Product function | ||
● I&M data | Yes | |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated as of version | V11 SP2 with HSP0024 / - | |
● STEP 7 configurable/integrated as of version | V5.5 SP2 with GSD file / - | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Input current | ||
Current consumption, max. | 60 mA; without load | |
Power loss | ||
Power loss, typ. | 1 W | |
Address area | ||
Address space per module | ||
● Address space per module, max. | 1 byte | |
Digital outputs | ||
Number of digital outputs | 4; > +60 °C number of simultaneously controllable outputs max. 2 x 0.25 A or max. 4 x 0.125 A, max. total current 0.5 A | |
Short-circuit protection | Yes | |
● Response threshold, typ. | 2.8 to 5.2 A | |
Limitation of inductive shutdown voltage to | Typ. L+ (-50 V) | |
Controlling a digital input | Yes | |
Switching capacity of the outputs | ||
● with resistive load, max. | 2 A | |
● on lamp load, max. | 10 W | |
Load resistance range | ||
● lower limit | 12 Ω | |
● upper limit | 3 400 Ω | |
Output current | ||
● for signal "1" rated value | 2 A | |
● for signal "0" residual current, max. | 0.1 mA | |
Output delay with resistive load | ||
● "0" to "1", max. | 50 µs | |
● "1" to "0", max. | 100 µs | |
Parallel switching of two outputs | ||
● for uprating | No | |
● for redundant control of a load | Yes | |
Switching frequency | ||
● with resistive load, max. | 100 Hz | |
● with inductive load, max. | 2 Hz | |
● on lamp load, max. | 10 Hz | |
Total current of the outputs | ||
● Current per module, max. | 8 A | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 200 m | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | Yes | |
Jitter, max. | 100 µs | |
Interrupts/diagnostics/status information | ||
Substitute values connectable | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
Diagnostic messages | ||
● Monitoring the supply voltage | Yes | |
● Wire-break | Yes | |
● Short-circuit | Yes | |
Diagnostics indication LED | ||
● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | |
● Channel status display | Yes; Green LED | |
● for module diagnostics | Yes; green/red DIAG LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | No | |
● between the channels and backplane bus | Yes | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC | |
Isolation | ||
Isolation tested with | 707 V DC | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin; Startup @ -25 °C | |
● horizontal installation, max. | 70 °C; = Tmax; > +60 °C number of simultaneously controllable outputs max. 2 x 0.25 A or max. 4 x 0.125 A, max. total current 0.5 A | |
● vertical installation, min. | -40 °C; = Tmin; Startup @ -25 °C | |
● vertical installation, max. | 50 °C; = Tmax | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 15 mm | |
Weights | ||
Weight, approx. | 30 g | |
last modified: | 02/03/2017 |