Technická data
Název:
SIPLUS ET200M IM153-4 PN IO HF
Popis:
SIPLUS ET200M IM 153-4 PN IO HF -40 ... +70 GRAD C START UP TEMP -25 DGR C WITH CONFORMAL COATING BASED ON 6ES7153-4BA00-0XB0 . DP, ET 200M INTERFACE FOR MAX. 12 S7-300 MODULES, SUPPORTS FAIL SAFE MODULES, HART MODULES SHARED DEVICE, MEDIUM REDUNDANCY PROTOCOL
Technické informace:
General information | ||
Vendor identification (VendorID) | 002AH | |
Device identifier (DeviceID) | 0302H | |
Supply voltage | ||
Rated value (DC) | ||
● 24 V DC | Yes | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
permissible range (ripple included), lower limit (DC) | 18.5 V | |
permissible range (ripple included), upper limit (DC) | 30.2 V | |
external protection for power supply lines (recommendation) | In a construction with grounded reference potential, a fuse is necessary for redundant interface modules (Recommendation: 2.5 A) | |
Mains buffering | ||
● Mains/voltage failure stored energy time | 5 ms | |
Input current | ||
Current consumption, max. | 600 mA; with 24 V DC supply | |
Inrush current, typ. | 4 A | |
I²t | 0.09 A²·s | |
Output voltage | ||
Rated value (DC) | 5 V | |
Output current | ||
for backplane bus (5 V DC), max. | 1.5 A | |
Power loss | ||
Power loss, typ. | 6 W | |
Address area | ||
Addressing volume | ||
● Inputs | 672 byte; Extended HART user data | |
● Outputs | 192 byte | |
Hardware configuration | ||
Number of modules per DP slave interface, max. | 12 | |
Protocols | ||
Bus protocol/transmission protocol | PROFINET IO | |
Interrupts/diagnostics/status information | ||
Diagnostics indication LED | ||
● Connection to network LINK (green) | Yes | |
● Transmit/receive RX/TX (yellow) | Yes | |
Isolation | ||
Isolation tested with | Between PROFINET and 24 V supply: 1 500 V AC, between functional grounding and 24 V supply: 500 V DC | |
Degree and class of protection | ||
Degree of protection acc. to EN 60529 | ||
● IP20 | Yes | |
Standards, approvals, certificates | ||
CE mark | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -40 °C; = Tmin; Startup @ -25 °C | |
● max. | 70 °C; = Tmax; Tmax > 60 °C output current for backplane bus (5 V DC) max. 0.9 A | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
● At cold restart, min. | -25 °C | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions | ||
Width | 40 mm | |
Height | 125 mm | |
Depth | 118 mm | |
Weights | ||
Weight, approx. | 215 g | |
last modified: | 02/01/2017 |