Název:
SIPLUS S7-300 SM336 F 6AI 15BIT
Popis:
SIPLUS ET 200M SM336 F 6AI 15BIT -25 ... +60 DEG C 70 DEG C WITH FORCED CONVECTION WITH CONFORMAL COATING BASED ON 6ES7336-4GE00-0AB0 . FAILSAFE ANALOG INPUTS FOR SIMATIC SAFETY, WITH HART SUPPORT, UP TO CATEGORY 4 (EN954-1)/ SIL3 (IEC61508)/ PLE (ISO13849), 1 X 20 PIN
Technické informace:
Supply voltage | ||
Rated value (DC) | 24 V; +/- 5 % | |
Reverse polarity protection | Yes | |
Input current | ||
From power supply L+, typ. | 150 mA | |
from backplane bus 5 V DC, max. | 90 mA | |
Power loss | ||
Power loss, typ. | 4.5 W | |
Analog inputs | ||
Number of analog inputs | 6 | |
permissible input current for current input (destruction limit), max. | 40 mA | |
Input ranges | ||
● Voltage | No | |
● Current | Yes | |
Input ranges (rated values), currents | ||
● 0 to 20 mA | Yes | |
● Input resistance (0 to 20 mA) | 150 Ω; typ. 150 ohms max. 175 ohms | |
● 4 mA to 20 mA | Yes | |
● Input resistance (4 mA to 20 mA) | 150 Ω; typ. 150 ohms max. 175 ohms | |
Cable length | ||
● shielded, max. | 1 000 m | |
Analog value generation for the inputs | ||
Integration and conversion time/resolution per channel | ||
● Integration time (ms) | 20 ms @ 50 Hz, 16.7 ms @ 60 Hz | |
● Interference voltage suppression for interference frequency f1 in Hz | f=n x (f1+-0.5%) | |
Encoder | ||
Connection of signal encoders | ||
● for current measurement as 2-wire transducer | Yes | |
● for current measurement as 4-wire transducer | Yes | |
Errors/accuracies | ||
Operational error limit in overall temperature range | ||
● Current, relative to input range, (+/-) | 0.3 %; 60 µA | |
Basic error limit (operational limit at 25 °C) | ||
● Current, relative to input range, (+/-) | 0.1 %; 20 µA | |
Interrupts/diagnostics/status information | ||
Diagnostic functions | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
Diagnostic messages | ||
● Diagnostic information readable | Yes | |
Diagnostics indication LED | ||
● Fail-safe operation | Yes | |
● Group error SF (red) | Yes | |
● Encoder supply Vs (green) | No | |
Potential separation | ||
Potential separation analog inputs | ||
● between the channels | Yes | |
● between the channels and backplane bus | Yes | |
● between the channels and the power supply of the electronics | Yes | |
Isolation | ||
Isolation tested with | 370V for 1 min | |
Standards, approvals, certificates | ||
CE mark | Yes | |
Highest safety class achievable in safety mode | ||
● acc. to EN 954 | 4 | |
● SIL acc. to IEC 61508 | SIL 3 | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -25 °C; = Tmin; Startup @ -25 °C | |
● max. | 60 °C; = T max; *+70 °C when forced convection at a minimum air speed of 0.3 m/s through the modules is ensured. If in the course of maintenance or automatic diagnosis it is determined that the admissible specified parameters have been exceeded, the modules should be subjected to a proof test (function check) by the manufacturer. | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | |
● At cold restart, min. | -25 °C | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; incl. condensation / frost permitted (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Connection method | ||
required front connector | 20-pin | |
Dimensions | ||
Width | 40 mm | |
Height | 125 mm | |
Depth | 120 mm | |
Weights | ||
Weight, approx. | 350 g | |
last modified: | 02/01/2017 |