Technická data
Název:
SIPLUS IM153-1
Popis:
SIPLUS DP ET200M IM153-1 -40...+70 DGR C START UP TEMP -25 DGR C WITH CONFORMAL COATING BASED ON 6ES7153-1AA03-0XB0 . INTERFACE FOR ET 200M, FOR MAX. 8 S7-300 MODULES
Technické informace:
General information | ||
Vendor identification (VendorID) | 801Dh | |
Supply voltage | ||
Rated value (DC) | ||
● 24 V DC | Yes | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
permissible range (ripple included), lower limit (DC) | 20.4 V | |
permissible range (ripple included), upper limit (DC) | 28.8 V | |
external protection for power supply lines (recommendation) | not necessary | |
Mains buffering | ||
● Mains/voltage failure stored energy time | 5 ms | |
Input current | ||
Current consumption, max. | 350 mA; at 24 V DC | |
Inrush current, typ. | 2.5 A | |
I²t | 0.1 A²·s | |
Output voltage | ||
Rated value (DC) | 5 V | |
Output current | ||
for backplane bus (5 V DC), max. | 1 A | |
Power loss | ||
Power loss, typ. | 3 W | |
Address area | ||
Addressing volume | ||
● Inputs | 128 byte | |
● Outputs | 128 byte | |
Hardware configuration | ||
Number of modules per DP slave interface, max. | 8 | |
Interfaces | ||
Interface physics, RS 485 | Yes | |
Interface physics, FOC | No | |
PROFIBUS DP | ||
● Node addresses | 1 to 125 permitted | |
● automatic detection of transmission rate | Yes | |
● Output current, max. | 90 mA | |
● Transmission rate, max. | 12 Mbit/s | |
● Transmission procedure | RS 485 | |
● SYNC capability | Yes | |
● FREEZE capability | Yes | |
● Direct data exchange (slave-to-slave communication) | Yes; Sender | |
● Connector type | 9-pin sub D socket | |
1. Interface | ||
DP slave | ||
● GSD file | (for DPV1) SIEM801D.GSD; SI01801D.GSG | |
● automatic baud rate search | Yes | |
Protocols | ||
Bus protocol/transmission protocol | PROFIBUS DP to EN 50170 | |
Isolation | ||
Isolation tested with | Isolation voltage 500 V | |
Degree and class of protection | ||
Degree of protection acc. to EN 60529 | ||
● IP20 | Yes | |
Standards, approvals, certificates | ||
CE mark | Yes | |
UL approval | Yes; File E239877 | |
FM approval | Yes; CofC 3028431 | |
RCM (formerly C-TICK) | Yes | |
KC approval | Yes | |
EAC (formerly Gost-R) | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -40 °C; = Tmin | |
● max. | 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
● At cold restart, min. | -25 °C | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Configuration | ||
Configuration software | ||
● STEP 7 | STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file | |
Dimensions | ||
Width | 40 mm | |
Height | 125 mm | |
Depth | 117 mm | |
Weights | ||
Weight, approx. | 360 g | |
last modified: | 02/01/2017 |