Technická data
Název:
SIPLUS S7-300 CP340 RS232
Popis:
SIPLUS S7-300 CP340 RS 232 -25 ... +70 DEGREES C BASED ON 6ES7340-1AH01-0AE0 . COMMUNICATIONS PROCESSOR WITH RS232C-INTERFACE (V.24) INCL. CONFIGURING PACKAGE ON CD
Technické informace:
Supply voltage | ||
Rated value (DC) | ||
● 24 V DC | No; Power supply via backplane bus 5V | |
Input current | ||
from backplane bus 5 V DC, max. | 165 mA | |
Power loss | ||
Power loss, typ. | 0.6 W | |
Power loss, max. | 0.85 W | |
Interfaces | ||
Number of interfaces | 1; Isolated | |
Interface physics, RS 232C (V.24) | Yes | |
Transmission rate, min. | 2.4 kbit/s | |
Transmission rate, max. | 19.2 kbit/s | |
Point-to-point | ||
● Cable length, max. | 15 m | |
● supported printers | HP-Deskjet, HP-Laserjet, IBM-Proprinter, user-defined | |
● Connector type | 9-pin sub D connector | |
Integrated protocol driver | ||
— 3964 (R) | Yes | |
— ASCII | Yes | |
— RK512 | No | |
— customer-specific drivers reloadable | No | |
Telegram length, max. | ||
— 3964 (R) | 1 024 byte | |
— ASCII | 1 024 byte | |
Transmission speed, RS 232 | ||
— with 3964 (R) protocol, max. | 19.2 kbit/s | |
— with ASCII protocol, max. | 9.6 kbit/s | |
— with printer driver, max. | 9.6 kbit/s | |
Standards, approvals, certificates | ||
CE mark | Yes | |
UL approval | Yes; File E239877 | |
FM approval | Yes; CofC 3028431 | |
RCM (formerly C-TICK) | Yes | |
KC approval | Yes | |
EAC (formerly Gost-R) | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -25 °C; = Tmin | |
● max. | 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Software | ||
Block | ||
● FB length in RAM, max. | 2 700 byte; Data communication, sending and receiving | |
Connection method | ||
Power supply | Over backplane bus | |
Dimensions | ||
Width | 40 mm | |
Height | 125 mm | |
Depth | 120 mm | |
Weights | ||
Weight, approx. | 300 g | |
last modified: | 02/01/2017 |