Technická data
Název:
SIPLUS S7-300 FM350-2
Popis:
SIPLUS S7-300 FM350-2 8 CHANNEL FOR MEDIAL STRESS WITH CONFORMAL COATING BASED ON 6ES7350-2AH01-0AE0 . COUNTER MODULE FM 350-2, 8 CHANNELS, 20 KHZ, 24V ENCODER FOR COUNTING, MEASURING FREQUENCIES, SPEED MEASUREMENT, PERIOD DURATION MEASUREMENT AND PROPORTIONING INCL. CONFIG. PACKAGE AND ELECTRONIC DOCU ON CD
Technické informace:
Supply voltage | ||
Auxiliary voltage 1L+, load voltage 2L+ | ||
● Rated value (DC) | 24 V | |
● permissible range, lower limit (DC) | 20.4 V | |
● permissible range, upper limit (DC) | 28.8 V | |
Input current | ||
from load voltage L+ (without load), max. | 150 mA | |
from backplane bus 5 V DC, max. | 100 mA | |
Encoder supply | ||
Type of output voltage | NAMUR-encoder supply: 8.2 V +/-2% | |
Short-circuit protection | Yes | |
Output current | ||
● Rated value | 200 mA | |
Power loss | ||
Power loss, typ. | 10 W | |
Digital inputs | ||
Number of digital inputs | 8 | |
Number of NAMUR inputs | 8 | |
Functions | 1 each for gate start/ gate stop | |
Input voltage | ||
● for signal "0" | -3 to +5V | |
● for signal "1" | 11 to 30.2 V | |
Input current | ||
● for signal "0", max. (permissible quiescent current) | 2 mA | |
● for signal "1", typ. | 9 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— at "0" to "1", max. | 50 µs | |
Cable length | ||
● shielded, max. | 100 m | |
Digital outputs | ||
Number of digital outputs | 8 | |
Short-circuit protection | Yes | |
Limitation of inductive shutdown voltage to | L+ (-40 V) | |
Output voltage | ||
● for signal "1", min. | L+ (-0.8 V) | |
Output current | ||
● for signal "1" rated value | 0.5 A | |
● for signal "0" residual current, max. | 0.5 mA | |
Output delay with resistive load | ||
● "0" to "1", max. | 300 µs | |
Switching frequency | ||
● with resistive load, max. | 500 Hz | |
● with inductive load, max. | 0.5 Hz | |
Total current of the outputs (per group) | ||
horizontal installation | ||
— up to 40 °C, max. | 4 A | |
— up to 60 °C, max. | 2 A | |
all other mounting positions | ||
— up to 40 °C, max. | 2 A | |
Cable length | ||
● shielded, max. | 600 m | |
● unshielded, max. | 100 m | |
Encoder | ||
Connectable encoders | ||
● Incremental encoder (asymmetrical) | Yes | |
● 24 V initiator | Yes | |
● 24 V directional element | Yes | |
● NAMUR encoder | Yes | |
● 2-wire sensor | Yes | |
NAMUR encoder | ||
● Input signal | to DIN 19 234 | |
● Input current for signal "0", max. | 1.2 mA | |
● Input current for signal "1", min. | 2.1 mA | |
● Input delay, max. | 50 µs | |
● Input frequency, max. | 20 kHz | |
● Cable length, shielded, max. | 100 m | |
Interrupts/diagnostics/status information | ||
Diagnostic functions | Yes; Diagnostic information readable | |
Alarms | ||
● Diagnostic alarm | Yes; Parameterizable | |
● Hardware interrupt | Yes; Parameterizable | |
Diagnostics indication LED | ||
● Group error SF (red) | Yes | |
Counter | ||
Counter input 24 V | ||
● Number | 8; 32 bit or ±31 bit | |
● Input voltage for signal "0" | -3 to +5V | |
● Input voltage for signal "1" | 11 to 30.2 V | |
● Input current for signal "0", max. (permissible quiescent current) | 2 mA | |
● Input current for signal "1", typ. | 9 mA | |
● Input delay, max. | 50 µs | |
● Counting frequency, max. | 20 kHz; Incremental encoder: 10 kHz | |
● Cable length, max. | 100 m | |
Potential separation | ||
Potential separation digital inputs | ||
● between the channels and backplane bus | Yes; and shielding | |
Potential separation digital outputs | ||
● between the channels and backplane bus | Yes; and shielding | |
Potential separation counter | ||
● between the channels and backplane bus | Yes; and shielding | |
Standards, approvals, certificates | ||
CE mark | Yes | |
UL approval | Yes; File E239877 | |
FM approval | Yes | |
RCM (formerly C-TICK) | Yes | |
KC approval | Yes | |
EAC (formerly Gost-R) | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | 0 °C; = Tmin | |
● max. | 60 °C; = Tmax | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Connection method | ||
required front connector | 1x 40-pin | |
Dimensions | ||
Width | 80 mm | |
Height | 125 mm | |
Depth | 120 mm | |
Weights | ||
Weight, approx. | 460 g | |
last modified: | 02/01/2017 |