SIPLUS S7-300 SM322 16DO -40 ... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7322-1FH00-0AA0 . DIGITAL OUTPUT OPTICALLY ISOLATED 16 DO, 120/230V AC, 1 A, 1 X 20 PIN
Technické informace:
Supply voltage | ||
Load voltage L1 | ||
● Rated value (AC) | 230 V; 120/230V AC | |
● permissible range, lower limit (AC) | 79 V | |
● permissible range, upper limit (AC) | 264 V | |
Input current | ||
from load voltage L1 (without load), max. | 2 mA | |
from backplane bus 5 V DC, max. | 200 mA | |
Power loss | ||
Power loss, typ. | 8.6 W | |
Digital outputs | ||
Number of digital outputs | 16 | |
Switching capacity of the outputs | ||
● on lamp load, max. | 50 W | |
Output current | ||
● for signal "1" rated value | 1 A | |
● for signal "1" minimum load current | 10 mA | |
● for signal "1" permissible surge current, max. | 20 A; with 2 half waves | |
● for signal "0" residual current, max. | 2 mA | |
Switching frequency | ||
● with resistive load, max. | 10 Hz | |
● with inductive load, max. | 0.5 Hz | |
● on lamp load, max. | 1 Hz | |
Total current of the outputs (per group) | ||
horizontal installation | ||
— up to 40 °C, max. | 4 A | |
— up to 60 °C, max. | 2 A | |
— up to 70 °C, max. | 1 A | |
vertical installation | ||
— up to 40 °C, max. | 2 A | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 600 m | |
Interrupts/diagnostics/status information | ||
Diagnostic functions | Yes; Fuse blown or load voltage missing | |
Alarms | ||
● Diagnostic alarm | No | |
Diagnostic messages | ||
● Wire-break | No | |
● Short-circuit | No | |
● Fuse blown | Yes | |
● missing load voltage | No | |
Diagnostics indication LED | ||
● Rated load voltage PWR (green) | No | |
● Fuse OK FSG (green) | Yes; Red LED for fuse | |
● Group error SF (red) | Yes | |
● Status indicator digital output (green) | Yes | |
Potential separation | ||
Potential separation digital outputs | ||
● between the channels, in groups of | 8 | |
● between the channels and backplane bus | Yes; Optocoupler | |
Isolation | ||
Isolation tested with | 4 000 V DC | |
Standards, approvals, certificates | ||
CE mark | Yes | |
UL approval | Yes; File E239877 | |
FM approval | Yes; CofC 3028431 | |
RCM (formerly C-TICK) | Yes | |
KC approval | Yes | |
EAC (formerly Gost-R) | Yes | |
Railway application | ||
● EN 50121-4 | No | |
● EN 50155 | No | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -40 °C; = Tmin | |
● max. | 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Connection method | ||
required front connector | 20-pin | |
Dimensions | ||
Width | 40 mm | |
Height | 125 mm | |
Depth | 120 mm | |
Weights | ||
Weight, approx. | 275 g | |
last modified: | 02/01/2017 |