Technická data
Název:
SIPLUS S7-300 SM322 8DO/24VDC 2A
Popis:
SIPLUS S7-300 SM322 (-1BF01) -25...+70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7322-1BF01-0AA0
Technické informace:
Supply voltage | ||
Load voltage L+ | ||
● Rated value (DC) | 24 V | |
● permissible range, lower limit (DC) | 20.4 V | |
● permissible range, upper limit (DC) | 28.8 V | |
Input current | ||
from load voltage L+ (without load), max. | 60 mA | |
from backplane bus 5 V DC, max. | 40 mA | |
Power loss | ||
Power loss, typ. | 6.8 W | |
Digital outputs | ||
Number of digital outputs | 8 | |
Limitation of inductive shutdown voltage to | L+ (-48 V) | |
Switching capacity of the outputs | ||
● on lamp load, max. | 10 W | |
Load resistance range | ||
● lower limit | 12 Ω | |
● upper limit | 4 kΩ | |
Output voltage | ||
● for signal "1", min. | L+ (-0.8 V) | |
Output current | ||
● for signal "1" rated value | 2 A | |
● for signal "1" minimum load current | 5 mA | |
● for signal "0" residual current, max. | 0.5 mA | |
Switching frequency | ||
● with resistive load, max. | 100 Hz | |
● with inductive load, max. | 0.5 Hz | |
● on lamp load, max. | 10 Hz | |
Total current of the outputs (per group) | ||
horizontal installation | ||
— up to 60 °C, max. | 4 A | |
— up to 70 °C, max. | 4 A | |
vertical installation | ||
— up to 40 °C, max. | 4 A | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 600 m | |
Interrupts/diagnostics/status information | ||
Diagnostic functions | No | |
Alarms | ||
● Diagnostic alarm | No | |
Diagnostic messages | ||
● Wire-break | No | |
● Short-circuit | No | |
● Fuse blown | No | |
● missing load voltage | No | |
Diagnostics indication LED | ||
● Rated load voltage PWR (green) | No | |
● Fuse OK FSG (green) | No | |
● Status indicator digital output (green) | Yes; per channel | |
Potential separation | ||
Potential separation digital outputs | ||
● between the channels | Yes | |
● between the channels, in groups of | 4 | |
● between the channels and backplane bus | Yes; Optocoupler | |
Permissible potential difference | ||
between different circuits | 75 V DC/60 V AC | |
Isolation | ||
Isolation tested with | 500 V DC | |
Standards, approvals, certificates | ||
CE mark | Yes | |
UL approval | Yes; File E239877 | |
FM approval | Yes | |
Railway application | ||
● EN 50121-4 | No | |
● EN 50155 | No | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -25 °C | |
● max. | 70 °C; = Tmax; 60 °C @ UL/cUL use | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Connection method | ||
required front connector | 20-pin | |
Dimensions | ||
Width | 40 mm | |
Height | 125 mm | |
Depth | 120 mm | |
Weights | ||
Weight, approx. | 190 g | |
last modified: | 02/01/2017 |