Technické informace:
Supply voltage | ||
Rated value (DC) | 24 V; 1L+ | |
Load voltage L+ | ||
● Rated value (DC) | 24 V; 2L+, 3L+ | |
Input current | ||
from supply voltage 1L+, max. | 100 mA | |
from load voltage 2L+ (without load), max. | 100 mA | |
from load voltage 3L+ (without load), max. | 100 mA | |
from backplane bus 5 V DC, max. | 100 mA | |
Power loss | ||
Power loss, typ. | 6 W | |
Digital outputs | ||
Number of digital outputs | 10 | |
Short-circuit protection | Yes | |
Switching capacity of the outputs | ||
● on lamp load, max. | 5 W | |
Output current | ||
● for signal "1" rated value | 2 A | |
● for signal "1" permissible range for 0 to 40 °C, min. | 7 mA | |
● for signal "1" permissible range for 0 to 40 °C, max. | 2.4 A | |
● for signal "1" permissible range for 40 to 60 °C, min. | 7 mA | |
● for signal "1" permissible range for 40 to 60 °C, max. | 2.4 A | |
● for signal "0" residual current, max. | 0.5 mA | |
Switching frequency | ||
● with resistive load, max. | 25 Hz | |
● with inductive load, max. | 25 Hz | |
● on lamp load, max. | 10 Hz | |
Total current of the outputs (per group) | ||
horizontal installation | ||
— up to 40 °C, max. | 10 A | |
— up to 60 °C, max. | 6 A | |
vertical installation | ||
— up to 40 °C, max. | 5 A | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 600 m | |
Interrupts/diagnostics/status information | ||
Alarms | ||
● Diagnostic alarm | Yes | |
Diagnostic messages | ||
● Diagnostic information readable | Yes | |
Diagnostics indication LED | ||
● Fail-safe operation | Yes | |
● Group error SF (red) | Yes | |
Potential separation | ||
Potential separation digital outputs | ||
● between the channels | Yes | |
● between the channels, in groups of | 5 | |
● between the channels and backplane bus | Yes | |
● between the channels and the power supply of the electronics | Yes | |
Isolation | ||
Isolation tested with | 370V for 1 min | |
Standards, approvals, certificates | ||
CE mark | Yes | |
UL approval | Yes; File E239877 | |
FM approval | Yes; CofC 3028431 | |
RCM (formerly C-TICK) | Yes | |
KC approval | Yes | |
EAC (formerly Gost-R) | Yes | |
Highest safety class achievable in safety mode | ||
● acc. to EN 954 | Cat. 4 | |
● SIL acc. to IEC 61508 | SIL 3 | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -25 °C | |
● max. | 60 °C; = T max; *+70 °C when forced convection at a minimum air speed of 0.3 m/s through the modules is ensured. If in the course of maintenance or automatic diagnosis it is determined that the admissible specified parameters have been exceeded, the modules should be subjected to a proof test (function check) by the manufacturer. | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Connection method | ||
required front connector | 40-pin | |
Dimensions | ||
Width | 40 mm | |
Height | 125 mm | |
Depth | 120 mm | |
Weights | ||
Weight, approx. | 330 g | |
last modified: | 02/01/2017 |