Technická data
Název:
SIPLUS S7-300 SM331 8AI - 40pol
Popis:
SIPLUS S7-300 SM331 40-POLE -25 ... +70 DGR C WITH CONFORMAL COATING CONFORMITY WITH EN50155 T1 CAT 1 KL A/B BASED ON 6ES7331-7NF00-0AB0 . ANALOG INPUT OPTIC. ISOLATED 8 AI; +/-5/10V, 1-5 V, +/-20MA, 0/4 UP TO 20MA, 16 BIT (55 MS), 1 COMMON POINT (50V COM.)
Technické informace:
Input current | ||
from backplane bus 5 V DC, max. | 130 mA | |
Power loss | ||
Power loss, typ. | 0.6 W | |
Analog inputs | ||
Number of analog inputs | 8 | |
permissible input voltage for voltage input (destruction limit), max. | 50 V; Permanent | |
permissible input current for current input (destruction limit), max. | 32 mA | |
Input ranges | ||
● Voltage | Yes | |
● Current | Yes | |
● Thermocouple | No | |
● Resistance thermometer | No | |
● Resistance | No | |
Input ranges (rated values), voltages | ||
● 0 to +10 V | No | |
● 1 V to 5 V | Yes | |
● Input resistance (1 V to 5 V) | 2 MΩ | |
● 1 V to 10 V | No | |
● -1 V to +1 V | No | |
● -10 V to +10 V | Yes | |
● Input resistance (-10 V to +10 V) | 2 MΩ | |
● -2.5 V to +2.5 V | No | |
● -250 mV to +250 mV | No | |
● -5 V to +5 V | Yes | |
● Input resistance (-5 V to +5 V) | 2 MΩ | |
● -50 mV to +50 mV | No | |
● -500 mV to +500 mV | No | |
● -80 mV to +80 mV | No | |
Input ranges (rated values), currents | ||
● 0 to 20 mA | Yes | |
● Input resistance (0 to 20 mA) | 250 Ω | |
● -20 mA to +20 mA | Yes | |
● Input resistance (-20 mA to +20 mA) | 250 Ω | |
● -3.2 mA to +3.2 mA | No | |
● 4 mA to 20 mA | Yes | |
● Input resistance (4 mA to 20 mA) | 250 Ω | |
Input ranges (rated values), thermocouples | ||
● Type B | No | |
● Type C | No | |
● Type E | No | |
● Type J | No | |
● Type K | No | |
● Type L | No | |
● Type N | No | |
● Type R | No | |
● Type S | No | |
● Type T | No | |
● Type U | No | |
● Type TXK/TXK(L) to GOST | No | |
Input ranges (rated values), resistance thermometer | ||
● Cu 10 | No | |
● Ni 100 | No | |
● Ni 1000 | No | |
● LG-Ni 1000 | No | |
● Ni 120 | No | |
● Ni 200 | No | |
● Ni 500 | No | |
● Pt 100 | No | |
● Pt 1000 | No | |
● Pt 200 | No | |
● Pt 500 | No | |
Input ranges (rated values), resistors | ||
● 0 to 150 ohms | No | |
● 0 to 300 ohms | No | |
● 0 to 600 ohms | No | |
● 0 to 6000 ohms | No | |
Cable length | ||
● shielded, max. | 200 m | |
Analog value generation for the inputs | ||
Measurement principle | integrating | |
Integration and conversion time/resolution per channel | ||
● Resolution with overrange (bit including sign), max. | 16 bit; Unipolar: 15/15/15/15 bit; bipolar: 15 bit + sign/15 bit + sign/15 bit + sign/15 bit + sign | |
● Integration time, parameterizable | Yes; 10/ 16.67/ 20/ 100 ms | |
● Interference voltage suppression for interference frequency f1 in Hz | 400 / 60 / 50 / 10 Hz | |
Encoder | ||
Connection of signal encoders | ||
● for current measurement as 2-wire transducer | Yes; with external transmitter; possible with separate supply for transmitter | |
● for current measurement as 4-wire transducer | Yes | |
Errors/accuracies | ||
Operational error limit in overall temperature range | ||
● Voltage, relative to input range, (+/-) | 0.1 %; @ Ucm = 0 V; @ Ucm = +-50 V: +/-0.7 % - @ 0 ... +60 °C; +/-0.5% @ Ucm = 0 V; @ Ucm = +-50 V: +/-0.9% - @ -25 ... +70 °C; | |
● Current, relative to input range, (+/-) | 0.3 %; @ Ucm = 0 V; @ Ucm = +-50 V: +/-0.4 % @ 0 ... +60 °C; +/-0.5% @ Ucm = 0 V; @ Ucm = +-50 V: +/-0.6% @ -25 ... +70 °C | |
Basic error limit (operational limit at 25 °C) | ||
● Voltage, relative to input range, (+/-) | 0.05 % | |
● Current, relative to input range, (+/-) | 0.05 % | |
Interrupts/diagnostics/status information | ||
Diagnostic functions | Yes; Parameterizable | |
Alarms | ||
● Diagnostic alarm | Yes; Parameterizable | |
● Limit value alarm | Yes; Parameterizable, channels 0 and 2 | |
Diagnostic messages | ||
● Diagnostic information readable | Yes | |
Diagnostics indication LED | ||
● Group error SF (red) | Yes | |
Potential separation | ||
Potential separation analog inputs | ||
● between the channels and backplane bus | Yes | |
Isolation | ||
Isolation tested with | 500 V DC | |
Standards, approvals, certificates | ||
CE mark | Yes | |
UL approval | Yes; File E239877 | |
FM approval | Yes | |
RCM (formerly C-TICK) | Yes | |
KC approval | Yes | |
EAC (formerly Gost-R) | Yes | |
Railway application | ||
● EN 50121-4 | No | |
● EN 50155 | Yes; T1 Category 1 Class A/B horizontal mounting position | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -25 °C; = Tmin | |
● max. | 70 °C; = Tmax; for use on railway vehicles according to EN 50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/UL hazardous use applies | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Extended ambient conditions | ||
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Connection method | ||
required front connector | 40-pin | |
Dimensions | ||
Width | 40 mm | |
Height | 125 mm | |
Depth | 117 mm | |
Weights | ||
Weight, approx. | 272 g | |
last modified: | 02/01/2017 |