Technická data
Název:
SIPLUS S7-300 SM334 4AE 2AA
Popis:
SIPLUS S7-300 SM334 4AI 2AO -25 ... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7334-0KE00-0AB0 . ANALOG MODULE OPTICALLY ISOLATED, 4AE/2AA, 12 BIT, 0-10V F. PT100 (CLIMAT RANGE -120 - 155 DEGR.) AND 10 KOHM MEASURING RANGE, 1 X 20 PIN
Technické informace:
Supply voltage | ||
Load voltage L+ | ||
● Rated value (DC) | 24 V | |
● Reverse polarity protection | Yes | |
Input current | ||
from supply and load voltage L+ (without load), max. | 80 mA | |
from backplane bus 5 V DC, max. | 60 mA | |
Power loss | ||
Power loss, typ. | 2 W | |
Analog inputs | ||
Number of analog inputs | 4 | |
● For voltage measurement | 2 | |
● For resistance measurement | 4 | |
permissible input voltage for voltage input (destruction limit), max. | 20 V; continuous; 75 V for max. 1 s (mark to space ratio 1:20) | |
Cycle time (all channels) max. | 85 ms | |
Input ranges | ||
● Voltage | Yes | |
● Current | No | |
● Thermocouple | No | |
● Resistance thermometer | Yes | |
● Resistance | Yes | |
Input ranges (rated values), voltages | ||
● 0 to +10 V | Yes | |
● Input resistance (0 to 10 V) | 100 kΩ | |
Input ranges (rated values), resistance thermometer | ||
● Pt 100 | Yes; only climatic range | |
Input ranges (rated values), resistors | ||
● 0 to 10000 ohms | Yes | |
Analog outputs | ||
Number of analog outputs | 2 | |
Voltage output, short-circuit protection | Yes | |
Voltage output, short-circuit current, max. | 10 mA | |
Output ranges, voltage | ||
● 0 to 10 V | Yes | |
Load impedance (in rated range of output) | ||
● with voltage outputs, min. | 2.5 kΩ | |
● with voltage outputs, capacitive load, max. | 1 µF | |
Cable length | ||
● shielded, max. | 100 m | |
Analog value generation for the inputs | ||
Integration and conversion time/resolution per channel | ||
● Resolution with overrange (bit including sign), max. | 12 bit | |
● Integration time (ms) | 16,67 / 20 ms | |
Analog value generation for the outputs | ||
Integration and conversion time/resolution per channel | ||
● Resolution with overrange (bit including sign), max. | 12 bit | |
Settling time | ||
● for resistive load | 0.8 ms | |
● for capacitive load | 0.8 ms | |
Encoder | ||
Connection of signal encoders | ||
● for resistance measurement with two-wire connection | Yes | |
● for resistance measurement with three-wire connection | Yes | |
● for resistance measurement with four-wire connection | Yes | |
Errors/accuracies | ||
Operational error limit in overall temperature range | ||
● Voltage, relative to input range, (+/-) | 0.8 %; 0 to 10V | |
● Resistance, relative to input range, (+/-) | 3.7 %; 10 kOhm | |
● Resistance thermometer, relative to input range, (+/-) | 1.1 % | |
● Voltage, relative to output range, (+/-) | 1.1 % | |
Basic error limit (operational limit at 25 °C) | ||
● Voltage, relative to input range, (+/-) | 0.5 %; 0 to 10V | |
● Resistance, relative to input range, (+/-) | 2.8 %; 10 kOhm | |
● Resistance thermometer, relative to input range, (+/-) | 0.8 % | |
● Voltage, relative to output range, (+/-) | 0.85 % | |
Interrupts/diagnostics/status information | ||
Alarms | No | |
Diagnostic functions | No | |
Potential separation | ||
Potential separation analog inputs | ||
● between the channels and backplane bus | Yes | |
Potential separation analog outputs | ||
● between the channels and backplane bus | Yes | |
Isolation | ||
Isolation tested with | 500 V DC | |
Standards, approvals, certificates | ||
CE mark | Yes | |
UL approval | Yes; File E239877 | |
FM approval | Yes | |
RCM (formerly C-TICK) | Yes | |
KC approval | Yes | |
EAC (formerly Gost-R) | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● min. | -25 °C; = Tmin | |
● max. | 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Extended ambient conditions | ||
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Connection method | ||
required front connector | 20-pin | |
Dimensions | ||
Width | 40 mm | |
Height | 125 mm | |
Depth | 117 mm | |
Weights | ||
Weight, approx. | 200 g | |
last modified: | 02/01/2017 |