Technická data
Název:
SIPLUS S7-1500 DI 48VUC/125VDC HF
Popis:
SIPLUS S7-1500 DI 48VUC/125VDC -40 ... +70 DEG C STARTUP -25 DEG C WITH CONFORMAL COATING BASED ON 6ES7521-7EH00-0AB0 . 16 CHANNELS IN GROUPS OF 1; INPUT DELAY 0.05 ... 20MS; INPUT TYPE 3 (IEC 61131); DIAGNOSIS, PROCESSALARMS
Technické informace:
General information | ||
Product type designation | DI 16x24 ... 125VUC HF | |
Digital inputs | ||
Input voltage | ||
● Rated value (DC) | 24 V | |
● Rated value (AC) | 24 V | |
● for signal "0" | -5 ... +5 V | |
● for signal "1" | +11 V DC to +146 V DC | |
Input current | ||
● for signal "1", typ. | 3 mA; at 24 V DC | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin | |
● horizontal installation, max. | 70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C max. 4 inputs (no adjacent points) | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
last modified: | 02/01/2017 |