Technická data
Název:
SIPLUS S7-1500 DQ 16X24VDC/0.5A HF
Popis:
SIPLUS S7-1500 DQ 16X24VDC/0.5A -40 ... +70 GRAD C STARTUP -25 GRAD C MIT CONFORMAL COATING BASED ON 6ES7522-1BH01-0AB0 . 16 CHANNELS IN GROUPS OF 8, 4 A PER GROUP; SINGLE-CHANNEL DIAGNOSIS; SUBSTITUTE VALUE
Technické informace:
General information | ||
Product type designation | DQ 16x24VDC/0.5A HF | |
Firmware version | ||
● FW update possible | Yes | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
Operating mode | ||
● DQ | Yes | |
● DQ with energy-saving function | No | |
● PWM | No | |
● Oversampling | No | |
● MSO | Yes | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes; through internal protection with 7 A per group | |
Input current | ||
Current consumption, max. | 30 mA | |
Output voltage | ||
Rated value (DC) | 24 V | |
Power | ||
Power available from the backplane bus | 1.1 W | |
Power loss | ||
Power loss, typ. | 2 W | |
Digital outputs | ||
Number of digital outputs | 16 | |
Current-sourcing | Yes | |
Short-circuit protection | Yes; Clocked electronically | |
● Response threshold, typ. | 1 A | |
Limitation of inductive shutdown voltage to | L+ (-53 V) | |
Controlling a digital input | Yes | |
Switching capacity of the outputs | ||
● with resistive load, max. | 0.5 A | |
● on lamp load, max. | 5 W | |
Load resistance range | ||
● lower limit | 48 Ω | |
● upper limit | 12 kΩ | |
Output voltage | ||
● for signal "1", min. | L+ (-0.8 V) | |
Output current | ||
● for signal "1" rated value | 0.5 A | |
● for signal "1" permissible range, max. | 0.5 A | |
● for signal "0" residual current, max. | 0.5 mA | |
Output delay with resistive load | ||
● "0" to "1", max. | 100 µs | |
● "1" to "0", max. | 500 µs | |
Parallel switching of two outputs | ||
● for logic links | Yes | |
● for uprating | No | |
● for redundant control of a load | Yes | |
Switching frequency | ||
● with resistive load, max. | 100 Hz | |
● with inductive load, max. | 0.5 Hz; According to IEC 60947-5-1, DC-13 | |
● on lamp load, max. | 10 Hz | |
Total current of the outputs | ||
● Current per channel, max. | 0.5 A; see additional description in the manual | |
● Current per group, max. | 4 A; see additional description in the manual | |
● Current per module, max. | 8 A; see additional description in the manual | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 600 m | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | Yes | |
Execution and activation time (TCO), min. | 70 µs | |
Bus cycle time (TDP), min. | 250 µs | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Substitute values connectable | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
Diagnostic messages | ||
● Monitoring the supply voltage | Yes | |
● Wire-break | Yes | |
● Short-circuit | Yes | |
● Group error | Yes | |
Diagnostics indication LED | ||
● RUN LED | Yes; Green LED | |
● ERROR LED | Yes; Red LED | |
● Monitoring of the supply voltage (PWR-LED) | Yes; Green LED | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | Yes; Red LED | |
● for module diagnostics | Yes; Red LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | No | |
● between the channels, in groups of | 8 | |
● between the channels and backplane bus | Yes | |
Isolation | ||
Isolation tested with | 707 V DC (type test) | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin | |
● horizontal installation, max. | 70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C max. aggregate current 2 A per group | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Decentralized operation | ||
Prioritized startup | Yes | |
Dimensions | ||
Width | 35 mm | |
Height | 147 mm | |
Depth | 129 mm | |
Weights | ||
Weight, approx. | 230 g | |
last modified: | 02/01/2017 |