Technická data
Název:
SIPLUS S7-1500 DQ 8X230VAC/2A ST (TRIAC)
Popis:
SIPLUS S7-1500 DO 8X230VAC/2A S -40 ... +70 DEGREE C WITH CONFORMAL COATING BASED ON 6ES7522-5FF00-0AB0 . DIGITAL OUTPUT MODULE DQ 8 X 230VAC,2A,TRIAC; 8 CHANNELS IN GROUPS OF 1, 2A PER GROUP; SUBSTITUTE VALUE
Technické informace:
General information | ||
Product type designation | DQ 8x230 V AC/2A ST (triac) | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
Output voltage | ||
Rated value (AC) | 120/230V AC, 50/60 Hz | |
Power | ||
Power available from the backplane bus | 0.9 W | |
Power loss | ||
Power loss, typ. | 10.8 W | |
Digital outputs | ||
Number of digital outputs | 8; > +60 °C number of simultaneously controllable outputs max. 8x 0.25 A, max. total current 2 A | |
Switching capacity of the outputs | ||
● with resistive load, max. | 2 A | |
● on lamp load, max. | 50 W | |
Output voltage | ||
● for signal "1", min. | L1 (-1.5 V) at maximum output current; L1 (-8.5 V) at minimum output current | |
Output current | ||
● for signal "1" rated value | 2 A | |
● for signal "1" permissible range, min. | 10 mA | |
● for signal "1" permissible range, max. | 15 A; max. 1 AC cycle | |
● for signal "0" residual current, max. | 2 mA | |
Output delay with resistive load | ||
● "0" to "1", max. | 1 AC cycle | |
● "1" to "0", max. | 1 AC cycle | |
Parallel switching of two outputs | ||
● for logic links | No | |
● for uprating | No | |
● for redundant control of a load | Yes | |
Switching frequency | ||
● with resistive load, max. | 10 Hz | |
● with inductive load, max. | 0.5 Hz | |
● on lamp load, max. | 1 Hz | |
Total current of the outputs | ||
● Current per channel, max. | 2 A; = Tmax; > +60 °C number of simultaneously controllable outputs max. 8x 0.25 A, max. total current per group 2 A | |
● Current per group, max. | 2 A; = Tmax; > +60 °C number of simultaneously controllable outputs max. 8x 0.25 A, max. total current per group 2 A | |
● Current per module, max. | 10 A; = Tmax; > +60 °C number of simultaneously controllable outputs max. 8x 0.25 A, max. total current per group 2 A | |
Relay outputs | ||
● Size of motor starters according to NEMA, max. | 5 | |
Triac outputs | ||
● Size of motor starters according to NEMA, max. | 5 | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 600 m | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | No | |
Interrupts/diagnostics/status information | ||
Diagnostics function | No | |
Substitute values connectable | Yes | |
Alarms | ||
● Diagnostic alarm | No | |
Diagnostic messages | ||
● Monitoring the supply voltage | No | |
● Wire-break | No | |
● Short-circuit | No | |
● Fuse blown | No | |
Diagnostics indication LED | ||
● RUN LED | Yes; Green LED | |
● ERROR LED | Yes; Red LED | |
● Monitoring of the supply voltage (PWR-LED) | No | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | No | |
● for module diagnostics | Yes; Red LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | Yes | |
● between the channels, in groups of | 1 | |
● between the channels and backplane bus | Yes | |
● Between the channels and load voltage L1 | Yes | |
Permissible potential difference | ||
between different circuits | 250 V AC between the channels and the backplane bus; 500 V AC between the channels | |
Isolation | ||
Isolation tested with | 2500 V DC | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin | |
● horizontal installation, max. | 70 °C; = Tmax; > +60 °C number of simultaneously controllable outputs max. 8x 0.25 A, max. total current 2 A | |
● vertical installation, min. | -40 °C; = Tmin | |
● vertical installation, max. | 40 °C; = Tmax | |
Extended ambient conditions | ||
● relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | |
Relative humidity | ||
— With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance | ||
— against biologically active substances / conformity with EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
— against chemically active substances / conformity with EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
— against mechanically active substances / conformity with EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Decentralized operation | ||
Fast Startup supported | Yes; 500 ms | |
Dimensions | ||
Width | 35 mm | |
Height | 147 mm | |
Depth | 129 mm | |
Weights | ||
Weight, approx. | 290 g | |
last modified: | 02/01/2017 |