Technická data
Název:
SIPLUS S7-1500 16DQ 230VAC 2A RLY
Popis:
SIPLUS S7-1500 16DQ 230VAC 2A RLY -40 ... +70 °C Startup -25 °C with conformal coating BasedOn 6ES7522-5HH00-0AB0 . Digital output module DQ 16 X 230VAC / 2A ST; RELAY; 16 channels in groups of 2, 4A per group; Diagnosois;
Technické informace:
General information | ||
Product type designation | DQ 16x230VAC/2A ST (relay) | |
Firmware version | ||
● FW update possible | Yes | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
Engineering with | ||
● PROFIBUS as of GSD version/GSD revision | V1.0 / V5.1 | |
● PROFINET as of GSD version/GSD revision | V2.3 / - | |
Operating mode | ||
● DQ | Yes | |
● DQ with energy-saving function | No | |
● PWM | No | |
● Oversampling | No | |
● MSO | Yes | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Input current | ||
Current consumption, max. | 150 mA | |
Power | ||
Power available from the backplane bus | 0.8 W | |
Power loss | ||
Power loss, typ. | 5 W | |
Digital outputs | ||
Type of digital output | Relays | |
Number of digital outputs | 16 | |
Current-sinking | Yes | |
Current-sourcing | Yes | |
Short-circuit protection | No | |
Controlling a digital input | Yes | |
Switching capacity of the outputs | ||
● on lamp load, max. | 50 W (230 V AC), 5 W (24 V DC) | |
Output current | ||
● for signal "1" rated value | 2 A | |
● for signal "1" permissible range, min. | 10 mA; 10 V | |
● for signal "1" permissible range, max. | 2 A; thermal continuous current | |
● for signal "0" residual current, max. | 0 A | |
Parallel switching of two outputs | ||
● for logic links | Yes | |
● for uprating | No | |
● for redundant control of a load | Yes | |
Switching frequency | ||
● with resistive load, max. | 1 Hz | |
● with inductive load, max. | 0.5 Hz | |
● on lamp load, max. | 1 Hz | |
Total current of the outputs | ||
● Current per channel, max. | 2 A; see additional description in the manual | |
● Current per group, max. | 2 A; see additional description in the manual | |
● Current per module, max. | 32 A; see additional description in the manual | |
Relay outputs | ||
● Number of relay outputs | 16 | |
● Rated supply voltage of relay coil L+ (DC) | 24 V | |
● Current consumption of relays (coil current of all relays), max. | 150 mA | |
● external protection for relay outputs | Miniature circuit breaker B10 / B16 | |
● Contact connection (internal) | No | |
● Size of motor starters according to NEMA, max. | 5 | |
● Number of operating cycles, max. | see additional description in the manual | |
● Relay approved acc. to UL 508 | No | |
Switching capacity of contacts | ||
— with inductive load, max. | 2 A; see additional description in the manual | |
— with resistive load, max. | 2 A; see additional description in the manual | |
Cable length | ||
● shielded, max. | 1 000 m | |
● unshielded, max. | 600 m | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | No | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Substitute values connectable | Yes | |
Alarms | ||
● Diagnostic alarm | Yes | |
Diagnostic messages | ||
● Monitoring the supply voltage | Yes | |
● Wire-break | No | |
● Short-circuit | No | |
Diagnostics indication LED | ||
● RUN LED | Yes; Green LED | |
● ERROR LED | Yes; Red LED | |
● Monitoring of the supply voltage (PWR-LED) | Yes; Green LED | |
● Channel status display | Yes; Green LED | |
● for channel diagnostics | No | |
● for module diagnostics | Yes; Red LED | |
Potential separation | ||
Potential separation channels | ||
● between the channels | No | |
● between the channels, in groups of | 2 | |
● between the channels and backplane bus | Yes | |
● Between the channels and load voltage L+ | Yes | |
Permissible potential difference | ||
between different circuits | 250 V AC between the channels and the supply voltage L+; 250 V AC between the channels and the backplane bus; 500 V AC between the channels | |
Isolation | ||
Isolation tested with | Between the channels: 2 500 V DC; between the channels and backplane bus: 2 500 V DC; between L+ backplane bus 707 V DC (type test) | |
Ambient conditions | ||
Ambient temperature during operation | ||
● horizontal installation, min. | -40 °C; = Tmin; Startup @ -25 °C | |
● horizontal installation, max. | 70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C max. 8 outputs (no adjacent points) | |
● vertical installation, min. | -40 °C; = Tmin; Startup @ -25 °C | |
● vertical installation, max. | 40 °C | |
Relative humidity | ||
● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Decentralized operation | ||
Prioritized startup | Yes | |
Dimensions | ||
Width | 35 mm | |
Height | 147 mm | |
Depth | 129 mm | |
Weights | ||
Weight, approx. | 350 g | |
last modified: | 09/25/2017 |